D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 109 -
The unit offers full control for any brand and model of motorized circuit breakers (MCB).
The MCB control is performed through 3 digital output functions, namely Open, Close and Undervoltage
coil controls. Only 2 of these outputs are used in a single application.
Any digital output can be assigned to MCB control signals through programming menu.
The MCB CLOSE sequence is below:
Activate UV output, wait for undervoltage coil timer (t
uv
)
Activate CLOSE output, wait for close pulse timer (t
cl
)
Deactivate CLOSE output
The MCB OPEN sequence is below:
Deactivate UV output
Activate OPEN output, wait for open pulse timer (t
op
)
Deactivate OPEN output
If MCB feedback input is defined and the MCB fails to
change position after the expiration of MCB Fail timer,
then a fault condition will occur.
Open Pulse, Close Pulse and Undervoltage Coil timers
are adjusted through programming menu.
22. MOTORIZED CIRCUIT BREAKER CONTROL
Содержание D-200 MK2
Страница 30: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 33: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 38: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 38 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Страница 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Страница 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...