D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 90 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
J1939 Speed Adjust
%
-100
+100
0.0
This parameter adjusts the speed of an
ECU controlled engine by +/- 8%.
High Air Inlet
Temperature Warning
Limit
°C
0
200
0
If the air inlet temperature measured
through ECU is over this limit, then a
high air inlet temperature warning will
occur.
High Air Inlet
Temperature Alarm Limit
°C
0
200
0
If the air inlet temperature measured
through ECU is over this limit, then a
high air inlet temperature
shutdown/loaddump alarm will occur.
High Air Inlet
Temperature Alarm
Action
-
0
1
0:
shutdown alarm
1:
loaddump alarm
Low Coolant Level
Warning Limit
%
0
100
0
If the coolant level measured through
ECU is below this limit, then a low
coolant level warning will occur.
Low Coolant Level Alarm
Limit
%
0
100
0
If the coolant level measured through
ECU is below this limit, then a low
coolant level shutdown/loaddump alarm
will occur.
Low Coolant Level Alarm
Action
-
0
1
0
0:
shutdown alarm
1:
loaddump alarm
Battery Charge Run
Voltage
V-DC
0
35.0
0
If the battery voltage goes below this
limit the engine will be automatically
started in order to charge the battery
using the charge alternator.
Battery Charge Run
Timer
min
0
1200
0
If the battery voltage goes below the
Battery Charge Run Voltage limit, the
engine will be automatically run during
this period in order to charge the
battery using the charge alternator.
Oil Pump Stop Pressure
bars
0
20
0
The oil pump is activated prior to the
crank cycle and stopped when this
pressure level is reached.
If this value is set to zero, then the oil
pump is not activated.
Service Reset-1
-
0
1
0
0: no action
1: reset service-1 counters
Service Reset-2
-
0
1
0
0: no action
1: reset service-3 counters
Service Reset-3
-
0
1
0
0: no action
1: reset service-3 counters
Disable ECU speed
control
-
0
1
0
0: Engine speed checking is performed
with the RPM information coming from
the engine ECU unit.
1: the RPM information coming from the
engine ECU unit is not used for engine
speed checking.
J1939 SPN Mask
-
0
65535
0
The SPN number written to this
parameter is excuded from engine ECU
alarm list.
J1939 FMI Mask
-
0
65535
0
The FMI number written to this
parameter is excuded from engine ECU
alarm list
16.3. ENGINE PARAMETERS GROUP (continued)
Содержание D-200 MK2
Страница 30: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 33: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 38: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 38 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Страница 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Страница 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...