D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 22 -
The Charge terminal is both an input and output.
When the engine is ready to run, this terminal supplies the excitation current to the charge alternator.
The excitation circuit is equivalent to a 2W lamp.
The threshold voltages for warning and shutdown alarm are adjustable through program parameter.
Structure:
•
battery voltage output through 100 ohm resistor
•
voltage measurement input
Output current:
100mA @12VDC
200mA @24VDC
Voltage measurement
resolution:
0.1VDC
Voltage measurement
accuracy:
2% + 0.1V (0.9V @30VDC)
Charge Fail Warning
Threshold:
adjustable
Charge Fail Shutdown
Alarm Threshold:
adjustable
Open circuit voltage:
battery positive
Overvoltage protection:
> 500VDC continuous, with respect to battery negative
Reverse voltage
protection:
-30VDC with respect to battery negative
Structure:
Differential frequency measurement input
Input impedance:
50 k-ohms
Input voltage:
0.5VAC-RMS to 50VAC-RMS
Frequency range:
10Hz to 10 kHz
Resolution:
1 rpm
Accuracy:
0.2% + 1 r
pm (±3rpm @1500 rpm)
Flywheel teeth range:
1 to 500
Do not share MPU with other devices.
3.6. CHARGE INPUT TERMINAL
3.7. MAGNETIC PICKUP INPUT
Содержание D-200 MK2
Страница 30: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 33: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 38: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 38 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Страница 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Страница 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...