HSS001 Quick Start Guide
9
Connect HSS to External Alarm Light/Horn
(optional)
The HSS includes alarm terminals (source and load) that can be used to connect
an external light or horn. The alarm terminals are rated for 125 VAC/60 VDC
max./.5 mA max.
An alarm silence button is not included. You can wire an external relay to
function as an alarm silence button if this feature is necessary.
Connect the HSS to a Power Source
IMPORTANT:
When using the power cord included with the HSS, the power
cord must be plugged into a grounded socket-outlet. The socket outlet must
be installed near the HSS and be easily accessible.
Use the optional power supply kit (part no. 016-0181) when running your own
conduit. This kit includes an IEC 320/C13 AC power plug assembly that
features screw terminals and is rated at 10 Amps/250 Volts. The rated voltage
and current for the HSS001 are 120 VAC and 2 Amperes.
Configure/Change the HSM's STATIC IP Address
Follow this same procedure if it becomes necessary to change the HSM's IP
address.
1.
Connect a PS-2 keyboard and VGA monitor to the HSM. Ports for
connecting a keyboard and monitor are easily accessible and clearly
marked.
2.
Power up the HSS following the procedure outlined in the section "HSM
Start Up and Shutdown Procedures," p. 20.
3.
When the HSM is fully powered and booted up, a login prompt appears
on the monitor. Login as MGR.
4.
At the command prompt, type
change_ip xxx.xxx.xxx.xxx
(where
xxx.xxx.xxx.xxx represents the IP address of the HSM). Enter Y or N to
confirm the IP change.
5.
Reboot the HSM.
A.
Press the power down button on the HSM and watch the HSM's
LEDs. When the +CPU LED goes off, the HSM is fully powered down.
After the HSM has been powered down, it cannot be restarted for 10
seconds. All inputs are ignored until 10 seconds have passed.
B.
After 10 seconds have passed, press the power up button on the HSM
and watch the HSM's LEDs. When the ACT LED begins to blink, the
HSM is fully powered up.