Application Guidelines

11

AB141686422149en-US0401

Operating conditions

Refrigerant and lubricants

Motor supply

Compressor ambient  
temperature

General information

High ambient temperature

PVE

Low ambient temperature

Residual moisture

When choosing a refrigerant, different aspects 
must be taken into consideration:
• 

Legislation (now and in the future)

• 

Safety

• 

Application envelope in relation to expected 
running conditions

• 

Compressor capacity and efficiency

• 

Compressor manufacturer 
recommendations & guidelines

Additional points could influence the final choice:
• 

Environmental considerations

• 

Standardisation of refrigerants and 
lubricants

• 

Refrigerant cost

• 

Refrigerant availability

In case of enclosed fitting and high ambient 
temperature, it is recommend to check the 

temperature of power wires and conformity to 
their insulation specification.

Polyvinyl ether (PVE) is an innovative refrigeration 
lubricant for HFC refrigerant systems. PVE is as 
hygroscopic as existing polyolester lubricants 
(POE), but PVE does not chemically react with 
water; no acids are formed and compressor 
evacuation is easier.

The compressor technology applied in Danfoss 
VRJ scroll compressors in combination with PVE 
lubricant provides the best possible result in 
terms of reliability and compressor lifetime. 

Although the compressor itself can withstand 
low ambient temperature, the system may 
require specific design features to ensure safe 

and reliable operation. See below sections for 
recommendations.

Prior to shipment from the factory, every 
compressor is dehydrated, evacuated, and 
charged with dry nitrogen. Maximum residual 

moisture levels are 0.0082 oz. for model VRJ028, 
and 0.0120 oz. for VRJ035 and VRJ044.

VRJ scroll compressors can be operated only 
connected to the dedicated variable speed 
drive, at nominal voltages as indicated in “supply 

voltage” section. Under-voltage and over-voltage 
operation is allowed within the indicated voltage 
range.

VRJ scroll compressors can be applied from 
-13°F to 125°F ambient temperature. The 
compressors are designed as 100 % suction gas 

cooled without need for additional fan cooling. 
Ambient temperature has very little effect on the 
compressor performance

VRJ scroll compressor application range is 
influenced by several parameters which need to 
be monitored for a safe and reliable operation.

These parameters and the main 
recommendations for good practice and safety 
devices are explained hereunder:

Refrigerant and lubricants

 

Motor supply 
Compressor ambient temperature 
Application envelope

 (evaporating 

temperature, condensing temperature, return gas 
temperature)

Содержание VRJ

Страница 1: ...Danfoss Inverter scroll compressor VRJ For Residential Applications R410A Application Guidelines http danfoss us com...

Страница 2: ......

Страница 3: ...pply 11 Compressor ambient temperature 11 Application envelope 12 High and low pressure protection 13 Crankcase heating 13 Oil return management 13 On off cycling cycle rate limit 14 Start up sequence...

Страница 4: ...lect a compressor size that achieves the peak load system cooling capacity demand at its maximum speed Nominal cooling capacity select a compressor size that achieves the nominal system cooling capaci...

Страница 5: ...git serial number 12345678 A 25 B Plant assembly line code Month code Application Family refrigerant V Variable speed R Residential J R410A PVE lubricant Swept Volume Displacement in cc rev Model Vari...

Страница 6: ...ompressor isentropic efficiency rpm Hz Btu hr Ton High SEER conditions H VRJ028 3 Tons 3600 60 36700 3 06 66 2 4200 70 42700 3 56 64 9 VRJ035 4 Tons 3600 60 46400 3 87 67 6 4200 70 53400 4 45 65 1 VRJ...

Страница 7: ...1 161 5 16 18 UNC self tapping Recommended torque for mounting bolts 8 ft lbs 1ft lbs 0 433 9 40 4 x 0 75 0 78 3 750 5 06 4 38 2 74 2 80 34 31 45 14 4 32 3 750 7 491 7 509 9 40 7 491 7 509 15 53 Suct...

Страница 8: ...ording to UL requirements With VRJ compressors the LRA value is low because the variable speed drive reacts very rapidly far below 1 second The MCC value is the maximum at which the compressor can be...

Страница 9: ...ion will be not possible If compressor and drive T1 T2 and T3 terminals are not matching the compressor can go in reverse rotation This results in excessive noise no pressure differential between suct...

Страница 10: ...ive 97 23 EC Low voltage directive 73 23 EC 93 68 EC Internal free volume Manufacturer s declaration of incorporation ref EC Machines Directives 98 392 CE Contact Danfoss Products Internal free volume...

Страница 11: ...bricant provides the best possible result in terms of reliability and compressor lifetime Although the compressor itself can withstand low ambient temperature the system may require specific design fe...

Страница 12: ...controller software s The discharge temperature depends mainly on the combination of evaporating temperature condensing temperature and suction gas superheat and speed Discharge gas temperature should...

Страница 13: ...y switch loss of charge safety switch setting is given in the above table Either the LP safety switch must be a manual lockout device or an automatic switch wired into an electrical lockout circuit Th...

Страница 14: ...arts VRJ compressors start with a defined ramp up and stay at a fixed speed for some seconds Then the compressor speed increases up to the desired set point according to capacity request On off cyclin...

Страница 15: ...ide of the compressor during off cycle The upper loop also helps avoid condensed liquid refrigerant from draining back to the compressor when stopped see fig 2 The maximum elevation difference between...

Страница 16: ...ronic expansion valve for all air conditioning and heat pump applications with VRJ compressors An EXV has two key benefits it provides modulating control of the system under varying load conditions an...

Страница 17: ...onnected to the drive Water utilising systems Apart from residual moisture in the system after commissioning water could also enter the refrigeration circuit during operation Water in the system shall...

Страница 18: ...long the parts of the unit and structure Gas pulsation This tends to travel through the cooling medium i e the refrigerant The following sections will focus on the causes and methods of mitigation for...

Страница 19: ...constitutes the primary method for controlling structural vibration VRJ scroll compressors are designed to produce minimal vibration during operations The use of rubber isolators on the compressor ba...

Страница 20: ...ust be taken never drill holes into the pipe work after installation Compressors are provided with a lifting lug This lug should always be used to lift the compressor Once the compressor is installed...

Страница 21: ...lux is acidic and can cause substantial damage to the internal parts of the system and compressor The PVE oil used in VRJ compressors is highly hygroscopic and will rapidly absorb moisture from the ai...

Страница 22: ...sulation resistance must be greater than 1 megohm when measured with a 500 volt direct current megohm tester Each compressor motor is tested at the factory with a high potential voltage hi pot that ex...

Страница 23: ...ping US thread bolts washers and sleeves Industrial pack Ordering code numbers Compressors are not packed individually but are shipped all together on one pallet They can be ordered in quantities of f...

Страница 24: ...nd positioned us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spread across three continents Danfoss Inverter Scrolls Danfoss Turboc...

Отзывы: