Application Guidelines

21

AB141686422149en-US0401

Installation

Vacuum evacuation and  
moisture removal

When brazing the compressor fittings, do not 
overheat the compressor shell, which could 
severely damage certain internal components 
due to excessive heating. Use of a heat shield 
and/or a heat-absorbent compound is highly 
recommended. For brazing the suction and 
discharge connections, the following procedure 
is advised:

• 

Make sure that no electrical wiring is 
connected to the compressor.

• 

Protect the terminal box and compressor 
painted surfaces from torch heat damage 
(see diagram).

• 

Use only clean refrigeration-grade copper 
tubing and clean all connections.

• 

Purge nitrogen or CO2 through the 
compressor in order to prevent against 
oxidation and flammable conditions. The 
compressor should not be exposed to the 
open air for extended periods.

• 

Use of a double-tipped torch is 
recommended.

• 

Apply heat evenly to area A until the brazing 
temperature is reached. Move the torch 
to area B and apply heat evenly until the 
brazing temperature has been reached there 
as well, and then begin adding the brazing 
material. Move the torch evenly around 
the joint, in applying only enough brazing 
material to flow the full circumference of the 
joint.

• 

Move the torch to area C only long enough 
to draw the brazing material into the joint, 
but not into the compressor.

• 

Remove all remaining flux once the joint has 
been soldered with a wire brush or a wet 
cloth. Remaining flux would cause corrosion 
of the tubing.

Ensure that no flux is allowed to enter into the 
tubing or compressor. Flux is acidic and can cause 
substantial damage to the internal parts of the 
system and compressor. 

The PVE oil used in VRJ compressors is highly 
hygroscopic and will rapidly absorb moisture 
from the air. The compressor must therefore not 
be left open to the atmosphere for a long period 
of time. The compressor fitting plugs shall be 
removed just before brazing the compressor.

 Before eventual unbrazing the compressor 

or any system component, the refrigerant charge 
must be removed from both the high and low 
pressure sides. Failure to do so may result in 
serious personal injury. Pressure gauges must be 
used to ensure all pressures are at atmospheric 
level.

For more detailed information on the appropriate 
materials required for brazing or soldering, please 
contact the product manufacturer or distributor. 
For specific applications not covered herein, 
please contact Danfoss Commercial Compressors 
for further information.

Moisture obstructs the proper functioning 
of both the compressor and the refrigeration 
system. 

Air and moisture reduce service life and 
increase condensing pressure, which causes 
abnormally high discharge temperatures that 
are then capable of degrading the lubricating 
properties of the oil. The risk of acid formation 
is also increased by air and moisture, and this 
condition can also lead to copper plating. All 
these phenomena may cause both mechanical 

and electrical compressor failures. The typical 
method for avoiding such problems is a vacuum 
pump-down executed with a vacuum pump, thus 
creating a minimum vacuum of 0.02 in Hg (500 
µm Hg). Please refer to Bulletin “Vacuum pump 
down and dehydration procedure”. 

Be sure to follow all government regulations 
regarding refrigerant reclamation and storage.

Compressor connection

Heat shield

C

B

A

Содержание VRJ

Страница 1: ...Danfoss Inverter scroll compressor VRJ For Residential Applications R410A Application Guidelines http danfoss us com...

Страница 2: ......

Страница 3: ...pply 11 Compressor ambient temperature 11 Application envelope 12 High and low pressure protection 13 Crankcase heating 13 Oil return management 13 On off cycling cycle rate limit 14 Start up sequence...

Страница 4: ...lect a compressor size that achieves the peak load system cooling capacity demand at its maximum speed Nominal cooling capacity select a compressor size that achieves the nominal system cooling capaci...

Страница 5: ...git serial number 12345678 A 25 B Plant assembly line code Month code Application Family refrigerant V Variable speed R Residential J R410A PVE lubricant Swept Volume Displacement in cc rev Model Vari...

Страница 6: ...ompressor isentropic efficiency rpm Hz Btu hr Ton High SEER conditions H VRJ028 3 Tons 3600 60 36700 3 06 66 2 4200 70 42700 3 56 64 9 VRJ035 4 Tons 3600 60 46400 3 87 67 6 4200 70 53400 4 45 65 1 VRJ...

Страница 7: ...1 161 5 16 18 UNC self tapping Recommended torque for mounting bolts 8 ft lbs 1ft lbs 0 433 9 40 4 x 0 75 0 78 3 750 5 06 4 38 2 74 2 80 34 31 45 14 4 32 3 750 7 491 7 509 9 40 7 491 7 509 15 53 Suct...

Страница 8: ...ording to UL requirements With VRJ compressors the LRA value is low because the variable speed drive reacts very rapidly far below 1 second The MCC value is the maximum at which the compressor can be...

Страница 9: ...ion will be not possible If compressor and drive T1 T2 and T3 terminals are not matching the compressor can go in reverse rotation This results in excessive noise no pressure differential between suct...

Страница 10: ...ive 97 23 EC Low voltage directive 73 23 EC 93 68 EC Internal free volume Manufacturer s declaration of incorporation ref EC Machines Directives 98 392 CE Contact Danfoss Products Internal free volume...

Страница 11: ...bricant provides the best possible result in terms of reliability and compressor lifetime Although the compressor itself can withstand low ambient temperature the system may require specific design fe...

Страница 12: ...controller software s The discharge temperature depends mainly on the combination of evaporating temperature condensing temperature and suction gas superheat and speed Discharge gas temperature should...

Страница 13: ...y switch loss of charge safety switch setting is given in the above table Either the LP safety switch must be a manual lockout device or an automatic switch wired into an electrical lockout circuit Th...

Страница 14: ...arts VRJ compressors start with a defined ramp up and stay at a fixed speed for some seconds Then the compressor speed increases up to the desired set point according to capacity request On off cyclin...

Страница 15: ...ide of the compressor during off cycle The upper loop also helps avoid condensed liquid refrigerant from draining back to the compressor when stopped see fig 2 The maximum elevation difference between...

Страница 16: ...ronic expansion valve for all air conditioning and heat pump applications with VRJ compressors An EXV has two key benefits it provides modulating control of the system under varying load conditions an...

Страница 17: ...onnected to the drive Water utilising systems Apart from residual moisture in the system after commissioning water could also enter the refrigeration circuit during operation Water in the system shall...

Страница 18: ...long the parts of the unit and structure Gas pulsation This tends to travel through the cooling medium i e the refrigerant The following sections will focus on the causes and methods of mitigation for...

Страница 19: ...constitutes the primary method for controlling structural vibration VRJ scroll compressors are designed to produce minimal vibration during operations The use of rubber isolators on the compressor ba...

Страница 20: ...ust be taken never drill holes into the pipe work after installation Compressors are provided with a lifting lug This lug should always be used to lift the compressor Once the compressor is installed...

Страница 21: ...lux is acidic and can cause substantial damage to the internal parts of the system and compressor The PVE oil used in VRJ compressors is highly hygroscopic and will rapidly absorb moisture from the ai...

Страница 22: ...sulation resistance must be greater than 1 megohm when measured with a 500 volt direct current megohm tester Each compressor motor is tested at the factory with a high potential voltage hi pot that ex...

Страница 23: ...ping US thread bolts washers and sleeves Industrial pack Ordering code numbers Compressors are not packed individually but are shipped all together on one pallet They can be ordered in quantities of f...

Страница 24: ...nd positioned us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spread across three continents Danfoss Inverter Scrolls Danfoss Turboc...

Отзывы: