Application Guidelines

13

AB141686422149en-US0401

Operating conditions

Pressure settings

High pressure

Low pressure

High pressure ratio

Crankcase heating

Oil return management

R410A

Working pressure range high side

psig

119 - 645

Working pressure range low side

psig

28 - 202

Maximum high pressure safety switch setting

psig

653

Minimum low pressure safety switch setting 

psig

22

: LP safety switch shall never be bypassed

According to UL requirements, a high pressure 
safety switch is still mandatory in any system, 
even with high pressure transmitters connected 
and used via the variable speed drive.

HP switch settings shall not exceed the maximum 
service pressure of any system components. The 
high-pressure switch can be set to lower values 

depending on the application and ambient 
conditions. The HP switch must either be placed 
in a lockout circuit or consist of a manual reset 
device to prevent cycling around the high-
pressure limit. If a discharge valve is used, the HP 
switch must be connected to the service valve 
gauge port, which must not be isolated.

A low pressure (LP) safety switch is 
recommended. Deep vacuum operations of a 
scroll compressor can cause internal electrical 
arcing and scroll instability. Danfoss scroll 
compressors exhibit high volumetric efficiency 
and may draw very low vacuum levels, which 
could induce such a problem. The minimum 

low-pressure safety switch (loss of charge safety 
switch) setting is given in the above table. Either 
the LP safety switch must be a manual lockout 
device or an automatic switch wired into an 
electrical lockout circuit. The LP switch tolerance 
must not allow for vacuum operations of the 
compressor.

Scroll compressors are machines with fixed 
volume ratio, and operate more efficiently 
near the design pressure ratio. In the extreme, 
do not exceed a 7.5:1 pressure ratio (absolute 
discharge pressure to absolute suction pressure) 

for extended periods. The Danfoss VRJ scroll 
compressor is equipped with an internal pressure 
relief valve for protection against blocked 
condenser and fan failure conditions.

A crankcase heating function can be provided 
by injecting a DC current in the motor of the 
compressor, to keep the compressor warm, and 
avoid liquid migration during off cycle.

Refer to “Danfoss VRJ Installation and Operation 
instructions” for details.

A specific function can be enabled to secure 
the oil return to the compressor. When the 
compressor is running at minimum speed for 

extended periods, every half hour, speed will be 
increased to 2400 rpm for a 80 seconds period.

Suction and discharge pressure transmitters have 
to be installed and connected to the variable 
speed drive to ensure the compressor operates 
within the application envelope described above.

Refer to “Danfoss VRJ Installation and Operation 
instructions” for connection details, and to 
“Sensor Selection Guideline” manual for selection 
details and technical brochures about pressure 
transmitters.

High and low pressure  
protection

Содержание VRJ

Страница 1: ...Danfoss Inverter scroll compressor VRJ For Residential Applications R410A Application Guidelines http danfoss us com...

Страница 2: ......

Страница 3: ...pply 11 Compressor ambient temperature 11 Application envelope 12 High and low pressure protection 13 Crankcase heating 13 Oil return management 13 On off cycling cycle rate limit 14 Start up sequence...

Страница 4: ...lect a compressor size that achieves the peak load system cooling capacity demand at its maximum speed Nominal cooling capacity select a compressor size that achieves the nominal system cooling capaci...

Страница 5: ...git serial number 12345678 A 25 B Plant assembly line code Month code Application Family refrigerant V Variable speed R Residential J R410A PVE lubricant Swept Volume Displacement in cc rev Model Vari...

Страница 6: ...ompressor isentropic efficiency rpm Hz Btu hr Ton High SEER conditions H VRJ028 3 Tons 3600 60 36700 3 06 66 2 4200 70 42700 3 56 64 9 VRJ035 4 Tons 3600 60 46400 3 87 67 6 4200 70 53400 4 45 65 1 VRJ...

Страница 7: ...1 161 5 16 18 UNC self tapping Recommended torque for mounting bolts 8 ft lbs 1ft lbs 0 433 9 40 4 x 0 75 0 78 3 750 5 06 4 38 2 74 2 80 34 31 45 14 4 32 3 750 7 491 7 509 9 40 7 491 7 509 15 53 Suct...

Страница 8: ...ording to UL requirements With VRJ compressors the LRA value is low because the variable speed drive reacts very rapidly far below 1 second The MCC value is the maximum at which the compressor can be...

Страница 9: ...ion will be not possible If compressor and drive T1 T2 and T3 terminals are not matching the compressor can go in reverse rotation This results in excessive noise no pressure differential between suct...

Страница 10: ...ive 97 23 EC Low voltage directive 73 23 EC 93 68 EC Internal free volume Manufacturer s declaration of incorporation ref EC Machines Directives 98 392 CE Contact Danfoss Products Internal free volume...

Страница 11: ...bricant provides the best possible result in terms of reliability and compressor lifetime Although the compressor itself can withstand low ambient temperature the system may require specific design fe...

Страница 12: ...controller software s The discharge temperature depends mainly on the combination of evaporating temperature condensing temperature and suction gas superheat and speed Discharge gas temperature should...

Страница 13: ...y switch loss of charge safety switch setting is given in the above table Either the LP safety switch must be a manual lockout device or an automatic switch wired into an electrical lockout circuit Th...

Страница 14: ...arts VRJ compressors start with a defined ramp up and stay at a fixed speed for some seconds Then the compressor speed increases up to the desired set point according to capacity request On off cyclin...

Страница 15: ...ide of the compressor during off cycle The upper loop also helps avoid condensed liquid refrigerant from draining back to the compressor when stopped see fig 2 The maximum elevation difference between...

Страница 16: ...ronic expansion valve for all air conditioning and heat pump applications with VRJ compressors An EXV has two key benefits it provides modulating control of the system under varying load conditions an...

Страница 17: ...onnected to the drive Water utilising systems Apart from residual moisture in the system after commissioning water could also enter the refrigeration circuit during operation Water in the system shall...

Страница 18: ...long the parts of the unit and structure Gas pulsation This tends to travel through the cooling medium i e the refrigerant The following sections will focus on the causes and methods of mitigation for...

Страница 19: ...constitutes the primary method for controlling structural vibration VRJ scroll compressors are designed to produce minimal vibration during operations The use of rubber isolators on the compressor ba...

Страница 20: ...ust be taken never drill holes into the pipe work after installation Compressors are provided with a lifting lug This lug should always be used to lift the compressor Once the compressor is installed...

Страница 21: ...lux is acidic and can cause substantial damage to the internal parts of the system and compressor The PVE oil used in VRJ compressors is highly hygroscopic and will rapidly absorb moisture from the ai...

Страница 22: ...sulation resistance must be greater than 1 megohm when measured with a 500 volt direct current megohm tester Each compressor motor is tested at the factory with a high potential voltage hi pot that ex...

Страница 23: ...ping US thread bolts washers and sleeves Industrial pack Ordering code numbers Compressors are not packed individually but are shipped all together on one pallet They can be ordered in quantities of f...

Страница 24: ...nd positioned us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spread across three continents Danfoss Inverter Scrolls Danfoss Turboc...

Отзывы: