[131]
Reference 4-20mA
: Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
: -200% to +200% of par. 20-14
Maximum Reference/Feedb.
[133]
Motor cur. 4-20mA
: 0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
)
[134]
Torq.% lim 4-20 mA
: 0 - Torque limit (par. 4-16
Torque Limit Motor Mode
)
[135]
Torq.% nom 4-20 mA
: 0 - Motor rated torque
[136]
Power 4-20mA
: 0 - Motor rated power
[137]
Speed 4-20mA
: 0 - Speed High Limit (4-13 and 4-14)
[139]
Bus ctrl.
: 0–100%, (0–20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0–100%, (0–20 mA)
[142]
Bus ctrl 4-20mA t.o.
: 0 - 100%
[143]
Ext. Closed-loop 1 4-20 mA
: 0 - 100%
[144]
Ext. Closed-loop 2 4-20 mA
: 0 - 100%
[145]
Ext. Closed-loop 3 4-20 mA
: 0 - 100%
NOTE!
Values for setting the minimum reference is found in open-loop par.3-02
and for closed-loop par. 20-13
Minimum Reference/
Feedb.
- values for maximum reference for open-loop is found in par.3-03
and for closed-loop par. 20-14
Maximum Reference/
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale for the minimum output (0 or 4 mA) of the analog signal at terminal 42.
Set the value to be the
percentage
of the full range of the variable selected in par.6-50
.
6 How to program the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
6-40
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark