6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage/low current value set in
par.6-20
and par. 6-22
Terminal 54 Low Current
.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par.6-21
and par. 6-23
Terminal 54 High Current
.
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 54. A high time constant value improves damping, but also increases the
time delay through the filter.
This parameter cannot be adjusted while the motor is running.
6-27 Terminal 54 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live Zero monitoring. For example, this to be used
if the analog outputs are used as part of a de-central I/O system (e.g., when used not as part of
any adjustable frequency drive related control functions, but for feeding a building management
system with data).
[0]
Disabled
[1] *
Enabled
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an analog current output. A motor current of 20 mA corre-
sponds to I
max
.
[0] *
No operation
[100]
Output frequency
: 0–100 Hz, (0–20 mA)
[101]
Reference
: Minimum reference - Maximum reference, (0–20 mA)
[102]
Feedback
: -200% to +200% of par. 20-14
Maximum Reference/Feedb.
, (0–20 mA)
[103]
Motor current
: 0 - Inverter Max. Current (par. 16-37), (0–20 mA)
[104]
Torque rel to limit
: 0 - Torque limit (par. 4-16
Torque Limit Motor Mode
), (0–20 mA)
[105]
Torq relate to rated
: 0 - Motor rated torque, (0–20 mA)
[106]
Power
: 0 - Motor rated power, (0–20 mA)
[107]
Speed
: 0 - Speed High Limit (par.4-13
), (0–20 mA)
[113]
Ext. Closed-loop 1
: 0–100%, (0–20 mA)
[114]
Ext. Closed-loop 2
: 0–100%, (0–20 mA)
[115]
Ext. Closed-loop 3
: 0–100%, (0–20 mA)
[130]
Output freq. 4-20mA
: 0–100 Hz
VLT
®
HVAC Drive Instruction Manual
6 How to program the adjustable frequency
drive
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
6-39