Line Power Supply 3 x 380–480 V AC
P315
P355
P400
P450
Typical Shaft output at 400
V [kW]
315
355
400
450
Typical Shaft output at 460
V [HP]
450
500
600
600
Enclosure
IP21
E1
E1
E1
E1
EnclosureIP54
E1
E1
E1
E1
Enclosure
IP00
E2
E2
E2
E2
Output current
Continuous
(at 400 V) [A]
600
658
745
800
Intermittent (60 sec over-
load)
(at 400 V) [A]
660
724
820
880
Continuous
(at 460/ 480 V) [A]
540
590
678
730
Intermittent (60 sec over-
load)
(at 460/480 V) [A]
594
649
746
803
Continuous KVA
(at 400 V) [KVA]
416
456
516
554
Continuous KVA
(at 460 V) [KVA]
430
470
540
582
Max. input current
Continuous
(at 400 V) [A]
590
647
733
787
Continuous
(at 460/480 V) [A]
531
580
667
718
Max. cable size, line pow-
er, motor and load share
[mm
2
(AWG
2)
)]
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
Max. cable size, brake
[mm
2
(AWG
2)
)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses
[A]
1
700
900
900
900
Estimated power loss
at rated max. load [W]
4)
,
400 V
6790
7701
8879
9670
Estimated power loss
at rated max. load [W]
4)
,
460 V
6082
6953
8089
8803
Weight,
enclosure IP21, IP 54 [kg]
263
270
272
313
Weight,
enclosure IP00 [kg]
221
234
236
277
Efficiency
4)
0.98
Output frequency
0–600 Hz
Heatsink overtemp. trip
203°F [95°C]
Power card ambient trip
154°F [68°C]
8 Specifications
VLT
®
HVAC Drive Instruction Manual
8-6
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
8
Содержание VLT
Страница 8: ...1 Safety VLT HVAC Drive Instruction Manual 1 6 MG 11 A9 22 VLT is a registered Danfoss trademark 1...
Страница 152: ...7 Troubleshooting VLT HVAC Drive Instruction Manual 7 8 MG 11 A9 22 VLT is a registered Danfoss trademark 7...
Страница 174: ...8 Specifications VLT HVAC Drive Instruction Manual 8 22 MG 11 A9 22 VLT is a registered Danfoss trademark 8...