[1117]
XIF Revision
Shows the version of the external interface file of the Neuron C chip on the LON option.
[1118]
LonWorks Revision
[1501]
Running Hours
View the number of running hours of the motor.
[1502]
kWh Counter
View the line power consumption in kWh.
[1600]
Control Word
View the control word sent from the adjustable frequency drive via the serial communication port
in hex code.
[1601]
Reference [Unit]
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selected
unit.
[1602] *
Reference %
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in percent.
[1603]
Status Word
Present status word
[1605]
Main Actual Value [%]
View the two-byte word sent with the status word to the bus master reporting the main actual value.
[1609]
Custom Readout
View the user-defined readouts as defined in par. 0-30
Custom Readout Unit
, par. 0-31
Custom
Readout Min Value
and par. 0-32
Custom Readout Max Value
.
[1610]
Power [kW]
Actual power consumed by the motor in kW.
[1611]
Power [hp]
Actual power consumed by the motor in HP.
[1612]
Motor voltage
Voltage supplied to the motor.
[1613]
Frequency
[1614]
Motor Current
Phase current of the motor measured as effective value.
[1615]
Frequency [%]
Motor frequency, i.e., the output frequency from the adjustable frequency drive in percent.
[1616]
Torque [Nm]
Present motor load as a percentage of the rated motor torque.
[1617]
Speed [RPM]
Motor speed reference. Actual speed will depend on slip compensation being used (compensation
set in par. 1-62
Slip Compensation
). If not used, actual speed will be the value read in the display
minus motor slip.
[1618]
Motor Thermal
Thermal load on the motor, calculated by the ETR function. See also parameter group 1-9* Motor
Temperature.
[1622]
Torque [%]
Shows the actual torque produced, in percentage.
[1626]
[1627]
[1630]
DC Link Voltage
Intermediate circuit voltage in the adjustable frequency drive.
[1632]
Brake Energy /s
[1633]
Brake Energy /2 min
[1634]
Heatsink Temp.
Present heatsink temperature of the adjustable frequency drive. The cut-out limit is 203° ± 9°F [95°
± 5
°
C]; cutting back in occurs at 158° ± 9°F [70° ± 5
°
C].
[1635]
Inverter Thermal
[1636]
Inv. Nom. Current
Nominal current of the adjustable frequency drive
[1637]
Inv. Max. Current
Maximum current of the adjustable frequency drive
[1638]
SL Controller State
[1639]
Control Card Temp.
Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a percentage, i.e., the sum of analog/pulse/bus.
6 How to program the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
6-14
MG.11.A9.22 - VLT
®