NB!
If moving the input bars, the CTs must also be reconfigured.
1.
Label the CTs L1, L2 and L3 (L1 is leftmost when working from the front of the starter). Remove the cable ties and unscrew
the CTs from the bracket.
2.
Move the CT bracket to the top of the starter. Position the CTs for the correct phases, then screw the CTs to the bracket. For
models MCD5-0360C - MCD5-0930, the CTs must be placed on an angle (the left hand legs of each CT will be on the top row
of holes and the right hand legs will be on the bottom tabs).
MCD 500 Operating Instruction
11 Bus Bar Adjustment Procedure
(MCD5-0360C - MCD5-1600C)