4.2.3 In-line Installation, Externally Bypassed
Non-bypassed models have dedicated bypass terminals, which allow the soft starter to continue providing protection and monitoring functions even when
bypassed via external contactor. The bypass contactor must be connected to the bypass terminals and controlled by a programmable output configured
to Run (see par. 4.1 - 4.9).
17
7
H
A
4
31
.1
1
M
3
F1
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1
L1B
L2B
L3B
KM2
34
33
KM2
KM1
Main contactor
KM2
Bypass contactor
F1
Fuses (optional)
NB!
The bypass terminals on MCD5-0245C are T1B, T2B, T3B. The bypass terminals on MCD5-0360C ~ MCD5-1600C are L1B, L2B, L3B.
The fuses can be installed on the input side if required.
4.3 Inside Delta Installation
NB!
When connecting the MCD 500 in inside delta configuration, always install a main contactor or shunt trip circuit breaker.
4 Electrical Installation
MCD 500 Operating Instruction
16
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
4
Содержание vlt soft starter mcd 500
Страница 48: ...6 Operation MCD 500 Operating Instruction 48 MG 17 K2 02 VLT is a registered Danfoss trademark 6...
Страница 54: ...7 Programming MCD 500 Operating Instruction 54 MG 17 K2 02 VLT is a registered Danfoss trademark 7...
Страница 82: ...9 Troubleshooting MCD 500 Operating Instruction 82 MG 17 K2 02 VLT is a registered Danfoss trademark 9...
Страница 88: ...10 Specifications MCD 500 Operating Instruction 88 MG 17 K2 02 VLT is a registered Danfoss trademark 10...