5 minutes
10 minutes
30 minutes
1 hour
8-7 Graph Max Adj
Range:
Function:
400%*
[0% - 600%]
Adjusts the upper limit of the performance graph
8-8 Graph Min Adj
Range:
Function:
0%*
[0% - 600%]
Adjusts the lower limit of the performance graph.
8-9 Mains Reference Voltage
Range:
Function:
400 V*
[100 - 690 V]
Sets the nominal voltage for the LCP's monitoring functions. This is used to calculate motor kilowatts
and kilovolt amperes (kVA), but does not affect the MCD 500's motor control protection.
Enter the measured mains voltage.
7.13 Restricted Parameters
15-1 Access Code
Range:
Function:
0000*
[0000 - 9999]
Sets the access code to enter the simulation tools and counter resets or the restricted section of the
Programming Menu (parameter group 15 and higher).
Use the
BACK
and
OK
buttons to select which digit to alter and use the
▲
and
▼
buttons to change
the value.
NB!
In the event of a lost access code, contact your supplier for master access code
that allows you to re-program a new access code.
15-2 Adjustment Lock
Option:
Function:
Selects whether the LCP will allow parameters to be changed via the Programming Menu.
Read & Write
*
Allows users to alter parameter values in the Programming Menu
Read Only
Prevents users altering parameter values in the Programming Menu. Parameter values can still be
viewed.
No Access
Prevents users adjusting parameters in the Programming Menu unless an access code is entered.
NB!
Changes to the Adjustment Lock setting take effect only after the Programming
Menu has been closed.
15-3 Emergency Run
Option:
Function:
Selects whether the soft starter will permit emergency run operation. In emergency run, the soft
starter will start (if not already running) and continue to operate until emergency run ends, ignoring
stop commands and trips.
Emergency run is controlled using a programmable input.
7 Programming
MCD 500 Operating Instruction
74
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
7
Содержание vlt soft starter mcd 500
Страница 48: ...6 Operation MCD 500 Operating Instruction 48 MG 17 K2 02 VLT is a registered Danfoss trademark 6...
Страница 54: ...7 Programming MCD 500 Operating Instruction 54 MG 17 K2 02 VLT is a registered Danfoss trademark 7...
Страница 82: ...9 Troubleshooting MCD 500 Operating Instruction 82 MG 17 K2 02 VLT is a registered Danfoss trademark 9...
Страница 88: ...10 Specifications MCD 500 Operating Instruction 88 MG 17 K2 02 VLT is a registered Danfoss trademark 10...