10 Specifications
Supply
Mains voltage (L1, L2, L3)
MCD5-xxxx-T5
200 VAC - 525 VAC (
±
10%)
MCD5-xxxx-T7
380 VAC - 600 VAC (
±
10%) (inside delta connection)
MCD5-xxxx-T7
380 VAC - 690 VAC (
±
10%) (earthed star supply system only)
Control voltage (A4, A5, A6)
CV1 (A5, A6)
24 VAC/VDC (
±
20%)
CV2 (A5, A6)
110~120 VAC (+ 10% / - 15%)
CV2 (A4, A6)
220~240 VAC (+ 10% / - 15%)
Current consumption (maximum)
CV1
2.8 A
CV2 (110 - 120 VAC)
1 A
CV2 (220 - 240 VAC)
500 mA
Mains frequency
50/60 Hz (
±
10%)
Rated insulation voltage to earth
600 VAC
Rated impulse withstand voltage
4 kV
Form designation
Bypassed or continuous, semiconductor motor starter form 1
Short circuit capability
Coordination with semiconductor fuses
Type 2
Coordination with HRC fuses
Type 1
MCD5-0021B to MCD5-0105B
prospective current 10 kA
MCD5-0131B to MCD5-0215B
prospective current 18 kA
MCD5-0245C to MCD5-0927C
prospective current 85 kA
MCD5-1200C to MCD5-1600C
prospective current 100 kA
Electromagnetic capability (compliant with EU Directive 89/336/EEC)
EMC Emissions
IEC 60947-4-2 Class B and Lloyds Marine No 1 Specification
EMC Immunity
IEC 60947-4-2
Inputs
Input Rating
Active 24 VDC, 8 mA approx
Start (15, 16)
Normally open
Stop (17, 18)
Normally closed
Reset (25, 18)
Normally closed
Programmable input (11, 16)
Normally open
Motor thermistor (05, 06)
Trip >3.6 k
Ω
, reset <1.6k
Ω
Outputs
Relay Outputs
10A @ 250 VAC resistive, 5A @ 250 VAC AC15 pf 0.3
Programmable Outputs
Relay A (13, 14)
Normally open
Relay B (21, 22, 24)
Changeover
Relay C (33, 34)
Normally open
Analog Output (07, 08)
0-20 mA or 4-20 mA (selectable)
Maximum load
600
Ω
(12 VDC @ 20 mA)
Accuracy
±
5%
24 VDC Output (16, 08) Maximum load
200 mA
Accuracy
±
10%
Environmental
Protection
MCD5-0021B - MCD5-0105B
IP20 & NEMA, UL Indoor Type 1
MCD5-0131B - MCD5-1600C
IP00, UL Indoor Open Type
Operating temperature
-10° C to 60° C, above 40° C with derating
Storage temperature
- 25° C to + 60° C
MCD 500 Operating Instruction
10 Specifications
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
89
10
Содержание vlt soft starter mcd 500
Страница 48: ...6 Operation MCD 500 Operating Instruction 48 MG 17 K2 02 VLT is a registered Danfoss trademark 6...
Страница 54: ...7 Programming MCD 500 Operating Instruction 54 MG 17 K2 02 VLT is a registered Danfoss trademark 7...
Страница 82: ...9 Troubleshooting MCD 500 Operating Instruction 82 MG 17 K2 02 VLT is a registered Danfoss trademark 9...