Symptom
Probable Cause
A reset does not occur after an Auto-Reset, when
using a remote 2-wire control.
-
The remote 2-wire start signal must be removed and reapplied for a re-start.
Remote start/stop command is overriding Auto
Start/Stop settings when using remote 2-wire con-
trol.
-
Auto Start/Stop function should only be used in HAND ON mode or in tandem with HAND OFF
mode, 3 and 4-wire control.
After selecting AAC the motor used an ordinary
start and/or the second start was different to the
first.
-
The first AAC start is current limit so that the starter can learn from the motor characteristics.
Subsequent starts use AAC.
Non-resettable THERMISTOR FAIL trip, when
there is a link between Thermistor input 05, 06 or
when the motor thermistor connected between
05, 06 is permanently removed.
-
The thermistor input is enabled once a link is fitted and short circuit protection has activated.
Remove the link then load the default parameter set. This will disable the thermistor input and
clear the trip.
Place a 1k2
Ω
resistor across the thermistor input.
Turn thermistor protection to 'Log only' (Par. 16-9).
Parameter settings cannot be stored.
-
Make sure you are saving the new value by pressing the
OK
button after adjusting a param-
eter setting. If you press
BACK
, the change will not be saved.
-
Check that the adjustment lock (Par. 15-2) is set to Read/Write. If the adjustment lock is on,
settings can be viewed but not changed. You need to know the security access code to change
the adjustment lock setting.
-
The EEPROM may be faulty on the Main Control PCB. A faulty EEPROM will also trip the soft
starter, and the LCP will display the message
Par. Out of Range
. Contact your local supplier
for advice.
MCD 500 Operating Instruction
9 Troubleshooting
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
87
9
Содержание vlt soft starter mcd 500
Страница 48: ...6 Operation MCD 500 Operating Instruction 48 MG 17 K2 02 VLT is a registered Danfoss trademark 6...
Страница 54: ...7 Programming MCD 500 Operating Instruction 54 MG 17 K2 02 VLT is a registered Danfoss trademark 7...
Страница 82: ...9 Troubleshooting MCD 500 Operating Instruction 82 MG 17 K2 02 VLT is a registered Danfoss trademark 9...
Страница 88: ...10 Specifications MCD 500 Operating Instruction 88 MG 17 K2 02 VLT is a registered Danfoss trademark 10...