5.12 Soft Braking
For high inertia loads the MCD 500 can be configured for soft braking.
In this application the MCD 500 is employed with forward run and braking contactors. When MCD 500 receives a start signal (button S1), it closes the
forward run contactor (KM1) and controls the motor according to the programmed primary motor settings.
When the MCD 500 receives a stop signal (button S2), it opens the forward run contactor (KM1) and closes the braking contactor (KM2) after a delay of
approximately 2-3 seconds (KT1). KA3 is also closed to activate the secondary motor settings, which should be user programmed for the desired stopping
performance characteristics.
When motor speed approaches zero, the external shaft rotation sensor (A2) stops the soft starter and opens the braking contactor (KM2).
3
17
7HA526.
10
6
5
6
4
2
3
1
KM2
KA1
KA2
KA3
KA4
KM1
M1
15
16
25
18
17
F1
KM2
KM1
KA3
S2
KA4
A2
KT1
KT1
KT2
KM1
KM2
KM1 KM2
S1
KA1
KA1
Y1
Y2
Y1
Y2
KA1
KT2
4/T2 6/T3 E
1/L1 3/L2 5/L3
2/T1
33
34
A4
A5
A6
05
06
KA3
KA2
S3
11
1
Control voltage (model dependent)
KA3
Brake relay
2
Remote control inputs
KA4
Rotation sensing relay
3
Motor thermistor input (PTC only)
KM1
Line contactor (Run)
4
Relay outputs
KM2
Line contactor (Brake)
5
3-phase supply
KT1
Run delay timer
6
Motor terminals
KT2
Brake delay timer
A2
Shaft rotation sensor
S1
Start contact
KA1
Run relay
S2
Stop contact
KA2
Start relay
S3
Reset contact
Parameter settings:
•
Par. 3-3
Input A Function
•
Select Motor Set Select - assigns Input A for Motor set selection
•
Set starting performance characteristics using the primary motor set (parameter group 1)
•
Set braking performance characteristics using the secondary motor settings (parameter group 7)
•
Par. 4-7
Relay C Function
•
Select Trip - assigns Trip function to Relay Output C
NB!
If the MCD-500 trips on supply frequency (Par. 16-5
Frequency
) when the braking contactor KM2 opens, modify the setting of Pars.
2-8 - 2-10.
MCD 500 Operating Instruction
5 Application Examples
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
45
5
Содержание vlt soft starter mcd 500
Страница 48: ...6 Operation MCD 500 Operating Instruction 48 MG 17 K2 02 VLT is a registered Danfoss trademark 6...
Страница 54: ...7 Programming MCD 500 Operating Instruction 54 MG 17 K2 02 VLT is a registered Danfoss trademark 7...
Страница 82: ...9 Troubleshooting MCD 500 Operating Instruction 82 MG 17 K2 02 VLT is a registered Danfoss trademark 9...
Страница 88: ...10 Specifications MCD 500 Operating Instruction 88 MG 17 K2 02 VLT is a registered Danfoss trademark 10...