7.3.2 Application Setups
The application setups menu makes it easy to configure the MCD 500 for common applications. The MCD 500 selects the parameters relevant to the
application and suggests a typical setting, and you can adjust each parameter to suit your exact requirements.
On the display the highlighted values are suggested values and the values indicated by a
▶
are the loaded values.
Always set par. 1-1
Motor FLC
to match the motor's nameplate full load current. The suggested value for motor FLC is the starter's minimum FLC.
Pump Centrifugal
Suggested Value
Compressor Recip
Suggested Value
Motor FLC
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Adaptive Control
Early Acceleration
5 seconds
350%
Adaptive Control
Late Deceleration
15 seconds
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Adaptive Control
Constant Acceleration
10 seconds
450%
Pump Submersible
Conveyor
Motor FLC
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Adaptive Control
Early Acceleration
5 seconds
350%
Adaptive Control
Late Deceleration
5 seconds
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Adaptive Control
Late Acceleration
15 seconds
400%
Adaptive Control
Constant Deceleration
5 seconds
Fan Damped
Crusher Rotary
Motor FLC
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Adaptive Control
Constant Acceleration
15 seconds
350%
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Adaptive Control
Constant Acceleration
20 seconds
400%
30 seconds
20 seconds
Fan Undamped
Crusher Jaw
Motor FLC
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Adaptive Control
Constant Acceleration
20 seconds
400%
30 seconds
20 seconds
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Adaptive Control
Constant Acceleration
30 seconds
450%
40 seconds
30 seconds
Compressor Screw
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Adaptive Control
Constant Acceleration
10 seconds
400%
MCD 500 Operating Instruction
7 Programming
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
57
7
Содержание vlt soft starter mcd 500
Страница 48: ...6 Operation MCD 500 Operating Instruction 48 MG 17 K2 02 VLT is a registered Danfoss trademark 6...
Страница 54: ...7 Programming MCD 500 Operating Instruction 54 MG 17 K2 02 VLT is a registered Danfoss trademark 7...
Страница 82: ...9 Troubleshooting MCD 500 Operating Instruction 82 MG 17 K2 02 VLT is a registered Danfoss trademark 9...
Страница 88: ...10 Specifications MCD 500 Operating Instruction 88 MG 17 K2 02 VLT is a registered Danfoss trademark 10...