4.5 Minimum and Maximum Current Settings
The MCD 500's minimum and maximum full load current settings depend on the model:
In-line Connection
Inside Delta Connection
Model
Minimum
Maximum
Minimum
Maximum
MCD5-0021B
5 A
23 A
7 A
34 A
MCD5-0037B
9 A
43 A
13 A
64 A
MCD5-0043B
10 A
50 A
15 A
75 A
MCD5-0053B
11 A
53 A
16 A
79 A
MCD5-0068B
15 A
76 A
23 A
114 A
MCD5-0084B
19 A
97 A
29 A
145 A
MCD5-0089B
20 A
100 A
30 A
150 A
MCD5-0105B
21 A
105 A
32 A
157 A
MCD5-0131B
29 A
145 A
44 A
217 A
MCD5-0141B
34 A
170 A
51 A
255 A
MCD5-0195B
40 A
200 A
60 A
300 A
MCD5-0215B
44 A
220 A
66 A
330 A
MCD5-0245B
51 A
255 A
77 A
382 A
MCD5-0360B
72 A
360 A
108 A
540 A
MCD5-0380B
76 A
380 A
114 A
570 A
MCD5-0428B
86 A
430 A
129 A
645 A
MCD5-0595B
124 A
620 A
186 A
930 A
MCD5-0619B
130 A
650 A
195 A
975 A
MCD5-0790B
158 A
790 A
237 A
1185 A
MCD5-0927B
186 A
930 A
279 A
1395 A
MCD5-1200B
240 A
1200 A
360 A
1800 A
MCD5-1410B
282 A
1410 A
423 A
2115 A
MCD5-1600B
320 A
1600 A
480 A
2400 A
4.6 Bypass Contactor
MCD 500 soft starters with model numbers MCD5-0021B - MCD5-0215B are internally bypassed and do not require an external bypass contactor.
MCD 500 soft starters with model numbers MCD5-0245C - MCD5-1600C are not internally bypassed and may be installed with an external bypass contactor.
Select a contactor with an AC1 rating greater than or equal to the full load current rating of the connected motor.
4.7 Main Contactor
A main contactor must be installed if the MCD 500 is connected to the motor in inside delta format and is optional for in-line connection. Select a contactor
with an AC3 rating greater than or equal to the full load current rating of the connected motor.
4.8 Circuit Breaker
A shunt trip circuit breaker may be used instead of a main contactor to isolate the motor circuit in the event of a soft starter trip. The shunt trip mechanism
must be powered from the supply side of the circuit breaker or from a separate control supply.
4.9 Power Factor Correction
If power factor correction is used, a dedicated contactor should be used to switch in the capacitors. Power factor correction capacitors must be connected
to the input side of the soft starter. Connecting power factor correction capacitors to the output side will damage the soft starter.
MCD 500 Operating Instruction
4 Electrical Installation
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
23
4
Содержание vlt soft starter mcd 500
Страница 48: ...6 Operation MCD 500 Operating Instruction 48 MG 17 K2 02 VLT is a registered Danfoss trademark 6...
Страница 54: ...7 Programming MCD 500 Operating Instruction 54 MG 17 K2 02 VLT is a registered Danfoss trademark 7...
Страница 82: ...9 Troubleshooting MCD 500 Operating Instruction 82 MG 17 K2 02 VLT is a registered Danfoss trademark 9...
Страница 88: ...10 Specifications MCD 500 Operating Instruction 88 MG 17 K2 02 VLT is a registered Danfoss trademark 10...