3.1.6 Recommended Design Rules
While designing Ethernet networks special attention and caution must be taken regarding active network components.
While designing a network for line topology it is important to notice that a small delay is added with each switch in the
line.
It is not recommended to connect more than 32 frequency converter in a line. Exceeding the recommended design rules,
may result in unstable or faulted communication.
130BC927.10
Illustration 3.9 Recommended Design Rules
How to Install
Operating Instructions
14
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
MG90U302
3
3