12-94 Broadcast Storm Protection
Range:
Function:
The “OFF” means that the filter is disabled - all
broadcast messages passes through. The value
“0%” means that no broadcast messages passes
through. A value of “10%” means that 10% of the
total bandwidth is allowed for broadcast
messages, if the amount of broadcast messages
increases above the 10% threshold, they will be
blocked.
-1
%
*
[-1 -
20 %]
12-95 Broadcast Storm Filter
Option:
Function:
Applies to
parameter 12-94 Broadcast
Storm Protection
; if the Broadcast Storm
Protection should also include Multicast
telegrams.
[0]
*
Broadcast only
[1]
Broadcast &
Multicast
12-96 Port Config
Enables/disables port-mirroring function. For troubleshooting
with a network analyzer tool.
Option:
Function:
[0]
Normal
No port-mirroring
[1]
Mirror Port 1 to 2
All network traffic on port 1 will
be mirrored to port 2.
[2]
Mirror Port 2 to 1
All network traffic on port 2 will
be mirrored to port 1.
[10]
Port 1 disabled
[11]
Port 2 disabled
[254]
Mirror Int. Port to 1
[255]
Mirror Int. Port to 2
12-98 Interface Counters
Range:
Function:
4000
*
[0 - 4294967295 ] Read only. Advanced Interface
counters, from built-in switch, can be
used for low-level troubleshooting,
The parameter shows a sum of port
1+port 2.
12-99 Media Counters
Range:
Function:
0
*
[0 - 4294967295 ] Read only. Advanced Interface counters,
from built-in switch, can be used for low-
level troubleshooting, The parameter
shows a sum of port 1+port 2.