8-14 Configurable Control Word CTW
Option:
Function:
Selection of control word bit 10 if it
is active low or active high.
[0]
None
[1]
*
Profile default
[2]
CTW Valid, active low
[3]
Safe Option Reset
[4]
PID error inverse
[5]
PID reset I part
[6]
PID enable
8-19 Product Code
Range:
Function:
Size
related
*
[0 -
2147483647 ]
Select [0] to readout the actual
fieldbus product code according
to the mounted fieldbus option.
Select [1] to readout the actual
Vendor ID.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus
Activates Start command via the serial communi-
cation port or fieldbus option.
[2] Logic
AND
Activates Start command via the fieldbus/serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTICE
Only selection
[0] Digital input
is available
when
1-10 Motor Construction
is set to
[1]
PM non-salient SPM
.
8-52 DC Brake Select
Option:
Function:
[0] Digital
input
Activates Start command via a digital input.
8-53 Start Select
Option:
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
input
Activates start command via a digital input.
[1] Bus
Activates start command via the serial communi-
cation port or fieldbus option.
[2] Logic
AND
Activates start command via the fieldbus/serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR
Activates start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option:
Function:
[0] Digital
input
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the fieldbus.
[1] Bus
Activates the Reverse command via the serial
communication port or fieldbus option.
[2] Logic AND Activates the Reverse command via the fieldbus/
serial communication port, AND additionally via
one of the digital inputs.
[3] Logic OR
Activates the Reverse command via the fieldbus/
serial communication port OR via one of the
digital inputs.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2] Logic
AND
Activates the set-up selection via the fieldbus/
serial communication port, AND additionally via
one of the digital inputs.
[3] Logic OR
Activate the set-up selection via the fieldbus/
serial communication port OR via one of the
digital inputs.
Parameters
Operating Instructions
MG90U302
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
45
8
8