No.
Description
Warning
Alarm/trip
Alarm/trip lock
Parameter reference
80
Drive Initialized to Default Value
X
81
CSIV corrupt
82
CSIV parameter error
85
Profibus/Profisafe Error
90
Encoder Loss
(X)
(X)
17-61 Feedback Signal Monitoring
91
Analogue input 54 wrong settings
X
S202
100-
199
See
Operating Instructions for MCO 305
243
Brake IGBT
X
X
244
Heatsink temp
X
X
X
245
Heatsink sensor
X
X
246
Pwr.card supply
X
X
247
Pwr.card temp
X
X
248
Illegal PS config
X
X
250
New spare part
X
14-23 Typecode Setting
251
New Type Code
X
X
Table 11.1 Alarm/Warning Code List
(X) Dependent on parameter
1) Cannot be Auto reset via 14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip
coasts the motor and can be reset by pressing [Reset] or
by making a reset by a
[1] digital input
(Parameter group
5-1* Digital I/O Mode
). The event that caused an alarm
cannot damage the frequency converter or cause
dangerous conditions. A trip lock is an action when an
alarm occurs, that can damage the frequency converter or
connected parts. A Trip Lock situation can only be reset by
a power cycling.
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Table 11.2 LED Indication
Warnings and Alarms
Operating Instructions
MG90U302
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
71