Bit (Hex)
Unit
diagnose
bit
PROFIBUS warning word
(
9-53 Profibus Warning Word
)
00000001
160
Connection with DP-master is not ok
00000002
161
Unused
00000004
162
FDL (Fieldbus Data link Layer) is not ok
00000008
163
Clear data command received
00000010
164
Actual value is not updated
00000020
165
Baudrate search
00000040
166
PROFIBUS ASIC is not transmitting
00000080
167
Initialising of PROFIBUS is not ok
00000100
152
Drive is tripped
00000200
153
Internal CAN error
00000400
154
Wrong configuration data from PLC
00000800
155
Wrong ID sent by PLC
00001000
156
Internal error occurred
00002000
157
Not configured
00004000
158
Timeout active
00008000
159
Warning 34 active
Table 10.18 FC 102/FC 202/FC 301/FC 302/FCD 302
Bit (Hex)
Comm. option STW (
16-84 Comm. Option STW
)
00000001
parameterization ok
00000002
configuration ok
00000004
clearmode active
00000008
baudrate search
00000010
waiting for parameterization
00000020
waiting for configuration
00000040
in data exchange
00000080
not used
00000100
not used
00000200
not used
00000400
not used
00000800
MCL2/1 connected
00001000
MCL2/2 connected
00002000
MCL2/3 connected
00004000
data transport active
00008000
not used
Table 10.19 FC 102/FC 202/FC 301/FC 302/FCD 302
NOTICE
16-84 Comm. Option STW
is not part of extended
diagnosis.
10.6 Warning and Alarm Messages
There is a clear distinction between alarms and warnings.
An alarm make the frequency converter enter a fault
condition. After the cause for the alarm has been cleared,
the master will have to acknowledge the alarm message
before the frequency converter can start operating again.
A warning condition triggers a warning which disappears
when condition returns to normal, without interfering with
the process.
Warnings
A single bit within a warning word represents warnings
within the frequency converter. Bit status
[0] False
means
no warning, while bit status
[1] True
means warning. Any
bit change in the warning word is notified by a change of
bit 7 in the status word.
Alarms
Following an alarm message, the frequency converter
enters fault condition. When the fault has been removed
and the controller has acknowledged the alarm message
by setting bit 7 in the control word, the frequency
converter resumes operation. A single bit within an alarm
word represents alarms within the frequency converter. Bit
status
[0] False
means no fault, while bit status
[1] True
means fault.
Troubleshooting
Operating Instructions
68
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
MG90U302