![background image](http://html.mh-extra.com/html/danfoss/vlt-midi-drive-fc-280/vlt-midi-drive-fc-280_programming-manual_506511072.webp)
4.9 Parameters: 8-** Communications and
Options
8-01 Control Site
Option:
Function:
The setting in this parameter overrides
the settings in
to
parameter 8-56 Preset Reference
[0]
*
Digital and
ctrl.word
Control by using both digital input and
control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword
only
Control by using control word only.
8-02 Control Source
Option:
Function:
Select the source of the control word.
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0] None
[1] FC Port
[2] FC USB
[3] Option A
8-03 Control Timeout Time
Range:
Function:
1 s
*
[0.1 -
6000 s]
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it indicates
that the serial communication has stopped. The
function that is selected in
parameter 8-04 Control Timeout Function
is then
carried out.
8-04 Control Timeout Function
Option:
Function:
[0]
*
Off
Select the timeout function. The timeout
function is activated when the control word
fails to be updated within the time period
specified in
parameter 8-03 Control Timeout
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
8-07 Diagnosis Trigger
Option:
Function:
[0]
*
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the installed fieldbus are visible in the LCP display.
Option:
Function:
[0]
*
FC profile
[1]
PROFIdrive profile
[7]
CANopen DSP 402
8-14 Configurable Control Word CTW
Option:
Function:
[0]
None
[1]
*
Profile default
[2]
CTW Valid, active low
[4]
PID error inverse
[5]
PID reset I part
[6]
PID enable
8-19 Product Code
Range:
Function:
Size
related
*
[0 -
2147483647]
Select 0 to read out the actual
fieldbus product code according
to the mounted fieldbus option.
Select 1 to read out the actual
vendor ID.
8-30 Protocol
Option:
Function:
Select the protocol for the integrated RS485
port.
[0]
*
FC
Communication according to the FC protocol.
[2]
Modbus RTU Communication according to the Modbus
RTU protocol.
8-31 Address
Range:
Function:
1
*
[ 0.0 - 247 ] Enter the address for the RS485 port. Valid
range: 1–126 for FC-bus, or 1–247 for Modbus.
8-32 Baud Rate
Option:
Function:
Select the baud rate for the RS485 port.
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
Parameter Descriptions
VLT
®
Midi Drive FC 280
70
Danfoss A/S © 12/2015 All rights reserved.
MG07C102
4
4
Содержание VLT Midi Drive FC 280
Страница 1: ...Programming Guide VLT Midi Drive FC 280 vlt drives danfoss com ...
Страница 2: ......
Страница 143: ...Index Programming Guide MG07C102 Danfoss A S 12 2015 All rights reserved 141 ...