5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Process Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
5-62 Pulse Output Max Freq 27
Range:
Function:
5000 Hz
*
[4 - 32000
Hz]
Set the maximum frequency for terminal
27, corresponding to the output variable
selected in
.
5-70 Term 32/33 Pulses Per Revolution
Range:
Function:
1024
*
[1 - 4096 ] Set the encoder pulses per revolution on the
motor shaft. Read the correct value from the
encoder.
5-71 Term 32/33 Encoder Direction
Option:
Function:
NOTICE
This parameter cannot be changed
while the motor is running.
Change the detected encoder rotation
direction without changing the wiring to the
encoder.
[0]
*
Clockwise
Sets channel A 90
°
(electrical degrees)
behind channel B after clockwise rotation of
the encoder shaft.
[1]
Counter
clockwise
Sets channel A 90
°
(electrical degrees) ahead
of channel B after clockwise rotation of the
encoder shaft.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 - 0xFFFFFFFF ] This parameter holds the state of the
digital outputs and relays controlled by
bus.
A logical 1 indicates that the output is
high or active.
A logical 0 indicates that the output is
low or inactive.
Bit 0–3
Reserved
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6–23
Reserved
Bit 24
Terminal 42 digital output
Bit 25
Terminal 45 digital output
Bit 26–31
Reserved
Table 4.4 Bit Functions
5-93 Pulse Out 27 Bus Control
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to the
output terminal 27 when the terminal is
configured as
[45] Bus Controlled
in
parameter 5-60 Terminal 27 Pulse Output
Variable
.
5-94 Pulse Out 27 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to the
output terminal 27 when the terminal is
configured as
[48] Bus Ctrl Timeout
in
parameter 5-60 Terminal 27 Pulse Output Variable
and a timeout is detected.
Parameter Descriptions
Programming Guide
MG07C102
Danfoss A/S © 12/2015 All rights reserved.
61
4
4