16-61 Terminal 53 Setting
Shows the setting of input terminal 53.
Option:
Function:
[1]
Voltage mode
[6]
Digital input
16-62 Analog Input 53
Range:
Function:
1
*
[0 - 20 ]
View the actual value at input 53.
16-63 Terminal 54 Setting
Option:
Function:
View the setting of input terminal 54.
[0] Current mode
[1] Voltage mode
16-64 Analog Input AI54
Range:
Function:
1
*
[0 - 20 ]
View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range:
Function:
0 mA
*
[0 - 20
mA]
View the actual value at output 42. The
value shown reflects the selections in
parameter 6-90 Terminal 42 Mode
and
parameter 6-91 Terminal 42 Analog Output
.
16-66 Digital Output
Range:
Function:
0
*
[0 - 15 ]
View the binary value of all digital outputs.
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual frequency rate on terminal 29.
16-68 Pulse Input 33 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual value of the frequency
applied at terminal 33 as an impulse input.
16-69 Pulse Output 27 [Hz]
Range:
Function:
0
*
[0 - 40000 ] View the actual value of impulses applied to
terminal 27 in digital output mode.
16-71 Relay Output
Range:
Function:
0
*
[0 - 65535 ]
View the settings of all relays.
16-72 Counter A
Range:
Function:
0
*
[-32768 -
32767 ]
View the present value of counter A. Counters are
useful as comparator operands, see
parameter 13-10 Comparator Operand
.
The value can be reset or changed either via
digital inputs (parameter group
5-1* Digital
Inputs
), or by using an SLC action
(
parameter 13-52 SL Controller Action
).
16-73 Counter B
Range:
Function:
0
*
[-32768 -
32767 ]
View the present value of counter B. Counters are
useful as comparator operands
(
parameter 13-10 Comparator Operand
).
The value can be reset or changed either via
digital inputs (parameter group
5-1* Digital
Inputs
) or by using an SLC action
(
parameter 13-52 SL Controller Action
).
16-74 Prec. Stop Counter
Shows the current value of the precise stop counter.
Range:
Function:
0
*
[0 - 2147483647 ]
16-80 Fieldbus CTW 1
Range:
Function:
0
*
[0 -
65535 ]
View the 2-byte control word (CTW) received
from the bus master. Interpretation of the CTW
depends on the fieldbus option installed and the
CTW profile selected in
parameter 8-10 Control
Word Profile
. For more information, see relevant
fieldbus manuals.
16-82 Fieldbus REF 1
Range:
Function:
0
*
[-32768 -
32767 ]
To set the reference value, view the 2-byte
word sent with the control word from the
bus master. For more information, refer to
the relevant fieldbus manual.
16-84 Comm. Option STW
Range:
Function:
0
*
[0 - 65535 ] View the extended fieldbus communication
option status word. For more information, refer
to the relevant fieldbus manual.
16-85 FC Port CTW 1
Range:
Function:
1084
*
[0 -
65535 ]
View the 2-byte control word (CTW) received
from the bus master. Interpretation of the
control word depends on the fieldbus option
installed and the control word profile
selected in
parameter 8-10 Control Word
Profile
.
Parameter Descriptions
Programming Guide
MG07C102
Danfoss A/S © 12/2015 All rights reserved.
101