0-12 Link Setups
Option:
Function:
The link ensures synchronising of the
Not
changeable during operation
parameter values
enabling shift from 1 set-up to another during
operation.
If the set-ups are not linked, a change between
them is not possible while the motor runs. Thus
the set-up change does not occur until the
motor is coasted.
[0]
Not
linked
Leaves parameters unchanged in both set-ups
and cannot be changed while the motor runs.
[20]
*
Linked
Copies
Not changeable during operation
parameters from 1 set-up to the other, so they
are identical in both set-ups.
0-14 Readout: Edit Set-ups / Channel
Range:
Function:
0
*
[-2147483647 - 2147483647 ]
0-16 Application Selection
Option:
Function:
[0]
*
None
[1]
Simple Process Close Loop
[2]
Local/Remote
[3]
Speed Open Loop
[4]
Simple Speed Close Loop
[5]
Multi Speed
[6]
OGD Function
0-20 Display Line 1.1 Small
Select a variable to display in line 1, left position.
Option:
Function:
[0]
[37]
Display Text 1
[38]
Display Text 2
[39]
Display Text 3
[748]
PCD Feed Forward
[953]
Profibus Warning Word
[1005]
Readout Transmit Error Counter
[1006]
Readout Receive Error Counter
[1501]
Running Hours
[1502]
kWh Counter
[1600]
Control Word
[1601]
Reference [Unit]
[1602]
*
Reference [%]
[1603]
Status Word
[1605]
Main Actual Value [%]
[1609]
Custom Readout
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor current
0-20 Display Line 1.1 Small
Select a variable to display in line 1, left position.
Option:
Function:
[1615]
Frequency [%]
[1616]
Torque [Nm]
[1618]
Motor Thermal
[1620]
Motor Angle
[1622]
Torque [%]
[1630]
DC Link Voltage
[1633]
Brake Energy /2 min
[1634]
Heatsink Temp.
[1635]
Inverter Thermal
[1636]
Inv. Nom. Current
[1637]
Inv. Max. Current
[1638]
SL Controller State
[1639]
Control Card Temp.
[1650]
External Reference
[1652]
Feedback[Unit]
[1653]
Digi Pot Reference
[1657]
Feedback [RPM]
[1660]
Digital Input
[1661]
Terminal 53 Setting
[1662]
Analog Input 53
[1663]
Terminal 54 Setting
[1664]
Analog Input AI54
[1665]
Analog Output 42 [mA]
[1666]
Digital Output
[1667]
Pulse Input 29[Hz]
[1668]
Pulse Input 33 [Hz]
[1669]
Pulse Output 27 [Hz]
[1671]
Relay Output
[1672]
Counter A
[1673]
Counter B
[1674]
Prec. Stop Counter
[1680]
Fieldbus CTW 1
[1682]
Fieldbus REF 1
[1684]
Comm. Option STW
[1685]
FC Port CTW 1
[1686]
FC Port REF 1
[1690]
Alarm Word
[1691]
Alarm Word 2
[1692]
Warning Word
[1693]
Warning Word 2
[1694]
Ext. Status Word
[1695]
Ext. Status Word 2
[1697]
Alarm Word 3
[1890]
Process PID Error
[1891]
Process PID Output
[1892]
Process PID Clamped Output
[1893]
Process PID Gain Scaled Output
[2117]
Ext. 1 Reference [Unit]
[2118]
Ext. 1 Feedback [Unit]
[2119]
Ext. 1 Output [%]
[3401]
PCD 1 Write For Application
Parameter Descriptions
VLT
®
Midi Drive FC 280
24