5-40 Function Relay
Option:
Function:
[75]
Logic rule 5
See parameter group
13-4* Logic Rules
.
If logic rule 5 in SLC is TRUE, the
output goes high. Otherwise, it goes
low.
[80]
SL digital output
A
See
parameter 13-52 SL Controller
Action
. Output A is low on
[32] Smart
Logic Action
. Output A is high on
[38]
Smart Logic Action
.
[81]
SL digital output
B
See
parameter 13-52 SL Controller
Action
. Output B is low on
[32] Smart
Logic Action
. Output B is high on
[38]
Smart Logic Action
.
[82]
SL digital output
C
See
parameter 13-52 SL Controller
Action
. Output C is low on
[32] Smart
Logic Action
. Output C is high on
[38]
Smart Logic Action
.
[83]
SL digital output
D
See
parameter 13-52 SL Controller
Action
. Output D is low on
[32] Smart
Logic Action
. Output D is high on
[38]
Smart Logic Action
.
[160] No alarm
The output is high when no alarm is
present.
[161] Running reverse
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
Running
AND
Reverse
).
[165] Local ref active
[166] Remote ref active
[167] Start command
activ
The output is high when there is an
active start command, and no stop
command is active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in hand-on mode.
[169] Drive in auto
mode
The output is high when the frequency
converter is in auto-on mode.
[170] Homing
Completed
The homing operation is completed.
This option is only effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
[171] Target Position
Reached
The target position is reached. This
option is only effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
[172] Position Control
Fault
A fault occurred in the positioning
process. Refer to
for details about the
fault. This option is only effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
5-40 Function Relay
Option:
Function:
[173] Position Mech
Brake
Selects mechanical control for
positioning. This option is only
effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
[190] Safe Function
active
[193] Sleep Mode
The frequency converter/system has
entered sleep mode. See parameter
group
22-4* Sleep Mode
.
[194] Broken Belt
Function
A broken belt condition has been
detected. See parameter group
22-4*
Sleep Mode
.
5-41 On Delay, Relay
Array [2](Relay 1 [0], Relay 2 [1])
Range:
Function:
0.01 s
*
[0.01 - 600
s]
Enter the delay of the relay cut-in time.
The relay only cuts in if the condition in
parameter 5-40 Function Relay
is uninter-
rupted during the specified time.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
Illustration 4.10 On Delay, Relay
5-42 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
Function:
0.01 s
*
[0.01 - 600 s] Enter the delay of the relay cut-out time.
Parameter Descriptions
Programming Guide
MG07C102