4.1.4 Extended Status Words
Bit
Hex
Dec
0
1
1
Ramping
Off
1
2
2
AMA running
Hand/Auto
2
4
4
Start CW/CCW
0
3
8
8
0
0
4
10
16
0
0
5
20
32
0
Relay 12 active
6
40
64
0
0
7
80
128
Output
current high
Control Ready
8
100
256
Output
current low
Drive Ready
9
200
512
0
Quick Stop
10
400
1024
0
DC Brake
11
800
2048
0
Stop
12
1000
4096
0
0
13
2000
8192
Braking
Freeze Output
Request
14
4000
16384
0
Freeze Output
15
8000
32768
OVC active
Jog Request
16
10000
65536
AC brake
Jog
17
20000
131072
0
Start request
18
40000
262144
0
Start
19
80000
524288
0
0
20
100000
1048576
0
Start Delay
21
200000
2097152
Local Ref./
Remote Ref.
Sleep
22
400000
4194304
0
Sleep boost
23
800000
8388608
0
Running
24
1000000
16777216
0
Bypass
25
2000000
33554432
0
Fire Mode
26
4000000
67108864
0
External Interlock
27
8000000
134217728
0
Firemodelimi-
texceed
28
10000000
268435456
0
FlyStart Active
29
20000000
536870912
0
0
30
40000000 1073741824
0
0
31
80000000 2147483648
Database
busy
0
Table 4.5
4.1.5 Fault Messages
WARNING/ALARM 2, Live zero error
This warning or alarm will only appear if programmed by
the user in
6-01 Live Zero Timeout Function
. The signal on
one of the analog inputs is less than 50% of the minimum
value programmed for that input. This condition can be
caused by broken wiring or faulty device sending the
signal.
Troubleshooting:
Check connections on all the analog input
terminals. Control card terminals 53 and 54 for
signals, terminal 55 common.
Check that the drive programming matches the
analog signal type.
WARNING/ALARM 4, Mains phase loss A phase is missing
on the supply side, or the line voltage imbalance is too
high. This message also appears for a fault in the input
rectifier on the adjustable frequency drive. Options are
programmed at
14-12 Function at Mains Imbalance
Troubleshooting: Check the supply voltage and supply
currents to the adjustable frequency drive.
WARNING/ALARM 7, DC over voltage
If the intermediate circuit voltage exceeds the limit, the
adjustable frequency drive trips after a time.
Troubleshooting:
Extend the ramp time
Activate functions in
WARNING/ALARM 8, DC under voltage
If the intermediate circuit voltage (DC) drops below the
undervoltage limit, the adjustable frequency drive trips
after a fixed time delay. The time delay varies with unit
size.
Troubleshooting:
Make sure that the supply voltage matches the
adjustable frequency drive voltage.
Perform Input voltage test
WARNING/ALARM 9, Inverter overloaded
The adjustable frequency drive is about to cut out because
of an overload (current too high for too long). The counter
for electronic, thermal inverter protection gives a warning
at 90% and trips at 100%, while giving an alarm. The
adjustable frequency drive
cannot
be reset until the
counter is below 90%.
The fault is that the adjustable frequency drive is
overloaded by more than 100% for too long.
Troubleshooting
VLT
®
HVAC Basic Drive Programming Guide
4-4
MG18B222 - VLT
®
is a registered Danfoss trademark
4
4
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...