5.1.8 6-** Analog In/Out
Par.
No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
6-0* Analog I/O Mode
6-00
Live Zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
6-01
Live Zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
6-1* Analog Input 53
6-10
Terminal 53 Low Voltage
0.07 V
All set-ups
TRUE
-2
Uint16
6-11
Terminal 53 High Voltage
10 V
All set-ups
TRUE
-2
Uint16
6-12
Terminal 53 Low Current
4 mA
All set-ups
TRUE
-5
Uint16
6-13
Terminal 53 High Current
20 mA
All set-ups
TRUE
-5
Uint16
6-14
Terminal 53 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-15
Terminal 53 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-16
Terminal 53 Filter Time Constant
0.01 s
All set-ups
TRUE
-2
Uint16
6-19
Terminal 53 mode
[1] Voltage mode
1 set-up
TRUE
-
Uint8
6-2* Analog Input 54
6-20
Terminal 54 Low Voltage
0.07 V
All set-ups
TRUE
-2
Uint16
6-21
Terminal 54 High Voltage
10 V
All set-ups
TRUE
-2
Uint16
6-22
Terminal 54 Low Current
4 mA
All set-ups
TRUE
-5
Uint16
6-23
Terminal 54 High Current
20 mA
All set-ups
TRUE
-5
Uint16
6-24
Terminal 54 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-25
Terminal 54 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-26
Terminal 54 Filter Time Constant
0.01 s
All set-ups
TRUE
-2
Uint16
6-29
Terminal 54 mode
[1] Voltage mode
1 set-up
TRUE
-
Uint8
6-7* Analog/Digital Output 45
6-70
Terminal 45 Mode
[0] 0-20 mA
All set-ups
TRUE
-
Uint8
6-71
Terminal 45 Analog Output
[0] No operation
All set-ups
TRUE
-
Uint8
6-72
Terminal 45 Digital Output
[0] No operation
All set-ups
TRUE
-
Uint8
6-73
Terminal 45 Output Min Scale
0 %
All set-ups
TRUE
-2
Uint16
6-74
Terminal 45 Output Max Scale
100 %
All set-ups
TRUE
-2
Uint16
6-76
Terminal 45 Output Bus Control
0 N/A
All set-ups
TRUE
0
Uint16
6-9* Analog/Digital Output 42
6-90
Terminal 42 Mode
[0] 0-20 mA
All set-ups
TRUE
-
Uint8
6-91
Terminal 42 Analog Output
[0] No operation
All set-ups
TRUE
-
Uint8
6-92
Terminal 42 Digital Output
[0] No operation
All set-ups
TRUE
-
Uint8
6-93
Terminal 42 Output Min Scale
0 %
All set-ups
TRUE
-2
Uint16
6-94
Terminal 42 Output Max Scale
100 %
All set-ups
TRUE
-2
Uint16
6-96
Terminal 42 Output Bus Control
0 N/A
All set-ups
TRUE
0
Uint16
6-98
Drive Type
0 N/A
1 set-up
FALSE
0
Uint8
Table 5.9
Parameter Lists
VLT
®
HVAC Basic Drive Programming Guide
5-8
MG18B222 - VLT
®
is a registered Danfoss trademark
5
5
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...