5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
[12]
Out of current
range
Motor current is outside range set in
and
[13]
Below current,
low
Motor current is lower than set in
[14]
Above current,
high
Motor current is higher than set in
[16]
Below speed,
low
[17]
Above speed,
high
[19]
Below feedback,
low
[20]
Above feedback,
high
[21]
Thermal warning The thermal warning turns on when the
temperature exceeds the limit in motor,
adjustable frequency drive or thermistor.
[22]
Ready, no
thermal warning
The adjustable frequency drive is ready
for operation and no over-temperature
warning is present.
[23]
Remote, ready,
no thermal
warning
The adjustable frequency drive is ready
for operation in auto mode, and no
over-temperature warning is present.
[24]
Ready, Voltage
OK
The adjustable frequency drive is ready
for operation and AC line voltage is
within the specified voltage range.
[25]
Reverse
Motor runs/is ready to run clockwise
when logic = 0 and counter clockwise
when logic = 1. Output changes as soon
as reversing signal is applied.
[26]
Bus OK
Active communication (no timeout) via
serial communication port.
[35]
External Interlock See digital input.
[36]
Control word bit
11
Bit 11 in the control word controls the
relay.
[37]
Control word bit
12
Bit 12 in control word controls relay.
[41]
Below reference,
low
[42]
Above ref, high
[45]
Bus Control
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
[60]
Comparator 0
See parameter group 13-1*. If
Comparator 0 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[61]
Comparator 1
See parameter group 13-1*. If
Comparator 2 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[62]
Comparator 2
See parameter group 13-1*. If
Comparator 2 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[63]
Comparator 3
See parameter group 13-1*. If
Comparator 3 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[64]
Comparator 4
See parameter group 13-1*. If
Comparator 4 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[65]
Comparator 5
See parameter group 13-1*. If
Comparator 5 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[70]
Logic rule 0
See parameter group 13-4*. If Logic
Rule 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
[71]
Logic rule 1
See parameter group 13-4*. If Logic
Rule 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
[72]
Logic rule 2
See parameter group 13-4*. If Logic
Rule 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
[73]
Logic rule 3
See parameter group 13-4*. If Logic
Rule 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
[74]
Logic rule 4
See parameter group 13-4*. If Logic
Rule 4 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
[75]
Logic rule 5
See parameter group 13-4*. If Logic
Rule 5 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
3-27
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...