[64]
Comparator 4
See parameter group 13-1*. If Comparator
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65]
Comparator 5
See parameter group 13-1*. If Comparator
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70]
Logic Rule 0
See parameter group 13-4*. If Logic Rule 0
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[71]
Logic Rule 1
See parameter group 13-4*. If Logic Rule 1
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[72]
Logic Rule 2
See parameter group 13-4*. If Logic Rule 2
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73]
Logic Rule 3
See parameter group 13-4*. If Logic Rule 3
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[74]
Logic Rule 4
See parameter group 13-4*. If Logic Rule 4
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[75]
Logic Rule 5
See parameter group 13-4*. If Logic Rule 5
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[80]
SL Digital
Output A
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [38]
Set dig. out. A
high is
executed. The input will go low whenever
the Smart Logic Action [32] Set dig. out. A
low is executed.
[81]
SL Digital
Output B
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [39]
Set dig. out. Bhigh
is executed.
The input will go low whenever the Smart
Logic Action [33]
Set dig. out. B low
is
executed.
[82]
SL Digital
Output C
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [40]
Set dig. out. C high
is executed.
The input will go low whenever the Smart
Logic Action [34]
Set dig. out. C low
is
executed.
[83]
SL Digital
Output D
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [41]
Set dig. out. D
high is
executed. The input will go low whenever
the Smart Logic Action [35]
Set dig. out. D
low
is executed.
[84]
SL Digital
Output E
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [42]
Set dig. out. E high
is executed.
The input will go low whenever the Smart
Logic Action [36]
Set dig. out. E low
is
executed.
[85]
SL Digital
Output F
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [43]
Set dig. out. F high
is executed.
The input will go low whenever the Smart
Logic Action [37]
Set dig. out. F low
is
executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running
reverse
The output is high when the adjustable
frequency drive is running counter-
clockwise (the logical product of the
status bits ‘running’ AND ‘reverse’).
[165] Local reference
active
The output is high when
3-13 Reference
Site
=
[2] Local
or when
3-13 Reference Site
=
[0] Linked to hand auto
at the same time
as the LCP is in [Hand On] mode.
[166] Remote
reference
active
The output is high when
3-13 Reference
Site
[1] or Linked to hand/auto [0]
while
the LCP is in [Auto on] mode.
[167] Start
command
active
The output is high when there is an
active Start command (i.e. via digital input
bus connection or [Hand on] or [Auto on],
and no Stop command is active).
[168] Drive in hand
mode
The output is high when the adjustable
frequency drive is in Hand on mode (as
indicated by the LED light above [Hand
on]).
[169] Drive in auto
mode
The output is high when the adjustable
frequency drive is in Hand on mode (as
indicated by the LED light above [Auto
on]).
[180] Clock Fault
The clock function has been reset to
default (2000-01-01) because of a power
failure.
[181] Preventive
Maintenance
One or more of the preventive
maintenance events programmed in
23-10 Maintenance Item
has passed the
time for the specified action in
23-11 Maintenance Action
.
[193] Sleep Mode
The adjustable frequency drive/system has
set to sleep mode. See parameter group
22-4*.
[194] Broken Belt
A Broken Belt condition has been
detected. This function must be enabled
in
22-60 Broken Belt Function
.
[196] Fire Mode
The adjustable frequency drive is
operating in Fire Mode. See parameter
group 24-0*
Fire Mode
.
[198] Drive Bypass
To be used as signal for activating an
external electromechanical bypass
switching the motor direct on line. See
24-1*
Drive Bypass
.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
3-25
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...