16-11 Power [hp]
Range:
Function:
0 hp
*
[0 - 1000 hp] View the DC link power in hp. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
16-12 Motor Voltage
Range:
Function:
0 V
*
[0 - 65535 V] View the motor voltage, a calculated value
used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
*
[0 - 6553.5 Hz] View the motor frequency, without
resonance dampening.
16-14 Motor current
Range:
Function:
0 A
*
[0 - 655.35 A] View the motor current measured as a
mean value, IRMS.
16-15 Frequency [%]
Range:
Function:
0 %
*
[0 - 6553.5 %]
16-18 Motor Thermal
Range:
Function:
0 %
*
[0 - 100 %]
3.12.3 16-3* Drive Status
16-30 DC Link Voltage
Range:
Function:
0 V
*
[0 - 65535 V]
View a measured value.
16-34 Heatsink Temp.
Range:
Function:
0 °C
*
[0 - 255 °C]
16-35 Inverter Thermal
Range:
Function:
0 %
*
[0 - 255 %]
16-36 Inv. Nom. Current
Range:
Function:
0 A
*
[0 - 655.35 A] View the inverter nominal current, which
should match the nameplate data on the
connected motor. The data are used for
motor protection, etc.
16-37 Inv. Max. Current
Range:
Function:
0 A
*
[0 - 655.35 A] View the inverter maximum current. The
data are used for calculation of adjustable
frequency drive protection, etc.
16-38 SL Controller State
Range:
Function:
0
*
[0 - 20 ] View the actual state of the Smart Logic
Controller (SLC).
3.12.4 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0 %
*
[-200 - 200 %]
16-52 Feedback[Unit]
Range:
Function:
0 ProcessCtrlUnit
*
[-4999 - 4999
ProcessCtrlUnit]
View the feedback
resulting from the
selection of scaling in
and
3.12.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[0 - 65535 ] View actual state of the digital inputs 18, 19,
27 and 29.
Bits definition
Bit 0
Unused
Bit 1
Unused
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6~15
Unused
Table 3.10
16-61 Terminal 53 Setting
Option:
Function:
View the setting of input terminal 53. Current
= 0; Voltage = 1.
[0] Current mode
[1] Voltage mode
Parameters
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
3-55
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...