3-16 Reference 2 Source
Option:
Function:
Select the input to be used for the
second reference signal.
,
and
define up to
three different reference signals. The
sum of these reference signals defines
the actual reference. See also
[0]
No function
[1]
Analog in 53
[2]
Analog in 54
[7]
Pulse input 29
[11] Local bus
reference
3-17 Reference 3 Source
Option:
Function:
Select the reference input to be used for
the third reference signal.
and
define up to three
different reference signals. The sum of
these reference signals defines the actual
reference.
This parameter cannot be adjusted while
the motor is running. The option
[1] PM
is
not accessible, if
=
[1] PM
.
[0]
No function
[1]
Analog in 53
[2]
Analog in 54
[7]
Pulse input 29
[11] Local bus
reference
3.4.3 3-4* Ramp 1
Configure the ramp parameter, ramping times, for each of
the two ramps (parameter group 3-4* and parameter
group 3-5*).
t
acc
t
dec
130BB801.10
P 3-*2
Ramp (X)
Down
Time (Dec)
P 4-14
High-limit
RPM
Reference
P 1-23
Motor
frequency
P 4-12
Low limit
Time
P 3-*1
Ramp (X)Up
Time (Acc)
Figure 3.6
3-41 Ramp 1 Ramp Up Time
Range:
Function:
Size
related
*
[0.05 -
3600 s]
Enter acceleration time from 0 Hz to
1-23 Motor Frequency if Asynchronous
motor is selected. Enter acceleration time
from 0 RPM to 1-25 Motor Nominal
Speed if PM motor is selected. Choose a
ramp-up time such that the output
current does not exceed the current limit
in
during ramping. See
ramp-down time in
3-42 Ramp 1 Ramp-
down Time
.
3-42 Ramp 1 Ramp Down Time
Range:
Function:
Size
related
*
[0.05 -
3600 s]
Enter deceleration time from 1-23 Motor
Frequency to 0 Hz if Asynchronous motor
is selected. Enter deceleration time from
1-25 Motor Nominal Speed to 0 RPM if
PM motor is selected. Choose a ramp-up
time such that the output current does
not exceed the current limit in
Current Limit during
ramping. See ramp-up time in
3-41 Ramp
1 Ramp-up Time
.
3.4.4 3-5* Ramp 2
Choosing ramp parameters, see parameter group 3-4*.
3-51 Ramp 2 Ramp Up Time
Range:
Function:
Size
related
*
[0.05 -
3600 s]
Enter acceleration time from 0 Hz to
1-23 Motor Frequency if Asynchronous
motor is selected. Enter acceleration time
from 0 RPM to 1-25 Motor Nominal
Speed if PM motor is selected. Choose a
ramp-down time such that the output
Parameters
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
3-15
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...