8-53 Start Select
Option:
Function:
Select control of the adjustable frequency drive
start function via the terminals (digital input).
NOTE!
This parameter is active only when
is set to
[0] Digital and
control wor
d.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus
Activates Start command via the serial communi-
cation port.
[2] Logic AND Activates Start command via the serial communi-
cation port, AND additionally via one of the
digital inputs.
[3] Logic OR
Activates Start command via the serial communi-
cation port OR via one of the digital inputs.
8-54 Reversing Select
Option:
Function:
Select control of the adjustable frequency drive
reverse function via the terminals (digital input)
and/or via the serial communication port.
NOTE!
This parameter is active only when
is set to [0] Digital and
control word.
[0] Digital
input
Activates Reverse command via a digital input.
[1] Bus
Activates Reverse command via the serial
communication port.
[2] Logic
AND
Activates Reverse command via the serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR
Activates Reverse command via the serial
communication port OR via one of the digital
inputs.
8-55 Set-up Select
Option:
Function:
Select control of the adjustable frequency drive
set-up selection via the terminals (digital input)
and/or via the serial communication port.
8-55 Set-up Select
Option:
Function:
NOTE!
This parameter is active only
when
is set to [0] Digital
and control word.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus
Activates the set-up selection via the serial
communication port.
[2] Logic
AND
Activates the set-up selection via the serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR
Activate the set-up selection via the serial
communication port OR via one of the digital
inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the adjustable frequency drive
Preset Reference selection via the terminals
(digital input) and/or via the serial communi-
cation port.
[0] Digital
input
Activates Preset Reference selection via a digital
input.
[1] Bus
Activates Preset Reference selection via the
serial communication port.
[2] Logic AND Activates Preset Reference selection via the
serial communication port, AND additionally via
one of the digital inputs.
[3] Logic OR
Activates the Preset Reference selection via the
serial communication port OR via one of the
digital inputs.
3.8.4 8-7* BACnet
8-70 BACnet Device Instance
Range:
Function:
1
*
[0 - 4194303 ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range:
Function:
127
*
[0 - 127 ] Define the address of the master which holds
the highest address in this network.
Decreasing this value optimizes polling for the
token.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-38
MG18B222 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...