Parameters
Function
Setting
6-12 Terminal 53
Low Current
4 mA*
6-13 Terminal 53
High Current
20 mA*
6-14 Terminal 53
Low Ref./Feedb.
Value
0 RPM
6-15 Terminal 53
High Ref./Feedb.
Value
1500 RPM
* = Default Value
Notes/comments:
Table 6.4 Analog Speed Reference (Current)
Parameters
Function
Setting
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[0] No
operation
5-19 Terminal 37
Digital Input
[1] Safe Stop
Alarm
* = Default Value
Notes/comments:
If
5-12 Terminal 27 Digital Input
is set to [0]
No operation
, a
jumper wire to terminal 27 is
not needed.
Table 6.5 Start/Stop Command with Safe Stop
Figure 6.1
Parameters
Function
Setting
5-10 Terminal 18
Digital Input
[9] Latched
Start
5-12 Terminal 27
Digital Input
[6] Stop
Inverse
* = Default Value
Notes/comments:
If
5-12 Terminal 27 Digital Input
is set to [0]
No operation
, a
jumper wire to terminal 27 is
not needed.
Table 6.6 Pulse Start/Stop
Figure 6.2
Application Examples
VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
6-2
MG21E122 - VLT® is a registered Danfoss trademark