Figure 5.10 Wiring Example for External Device Providing 0-10 V
Control Signal
5.3 Control
Terminal
Programming
Examples
Control terminals can be programmed.
•
Each terminal has specified functions it is capable
of performing
•
Parameters associated with the terminal enable
the function
•
For proper frequency converter functioning, the
control terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
See
Table 5.1
for control terminal parameter number and
default setting. (Default setting can change based on the
selection in
0-03 Regional Settings
.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to parameter
group 5-**
Digital In/Out Parameter Data Set
and
press [OK].
Figure 5.11
2.
Scroll to parameter group 5-1*
Digital Inputs
and
press [OK].
Figure 5.12
3.
Scroll to
5-10 Terminal 18 Digital Input
. Press [OK]
to access function choices. The default setting
Start
is shown.
Figure 5.13
5.4 International/North American Default
Parameter Settings
Setting
0-03 Regional Settings
[0] International
or
[1] North
America
changes the default settings for some parameters.
Table 5.1
lists those parameters that are affected.
Parameter
International
Default Parameter
Value
North American
Default Parameter
Value
0-03 Regional
Settings
International
North America
0-71 Date Format
DD-MM-YYYY
MM/DD/YYYY
0-72 Time Format
24 h
12 h
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage
230 V/400 V/575 V
208 V/460 V/575 V
1-23 Motor
Frequency
50 Hz
60 Hz
3-03 Maximum
Reference
50 Hz
60 Hz
3-04 Reference
Function
Sum
External/Preset
Programming
VLT® Automation VT Drive FC 322 D-Frame Instruction Manual