3.
Use navigation keys to scroll to parameter group
0-0*
Basic Settings
and press [OK].
Figure 3.2
4.
Use navigation keys to scroll to
0-03 Regional
Settings
and press [OK].
Figure 3.3
5.
Use navigation keys to select
International
or
North America
as appropriate and press [OK]. (This
changes the default settings for a number of
basic parameters. See
5.5 Parameter Menu
Structure
for a complete list.)
6.
Press [Quick Menu] on the LCP.
7.
Use the navigation keys to scroll to parameter
group
Q2 Quick Setup
and press [OK].
Figure 3.4
8.
Select language and press [OK]. Then enter the
motor data in
1-20 Motor Power [kW]
/
1-21 Motor
Power [HP]
through
1-25 Motor Nominal Speed
.
The information can be found on the motor
nameplate.
1-20 Motor Power [kW]
or
1-21 Motor
Power [HP]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
Figure 3.5
9.
A jumper wire should be in place between
control terminals 12 and 27. If this is the case,
leave
5-12 Terminal 27 Digital Input
at factory
default. Otherwise select
No Operation
. For
frequency converters with an optional Danfoss
bypass, no jumper wire is required.
10.
3-02 Minimum Reference
11.
3-03 Maximum Reference
12.
3-41 Ramp 1 Ramp Up Time
13.
3-42 Ramp 1 Ramp Down Time
14.
3-13 Reference Site
. Linked to Hand/Auto* Local
Remote.
This concludes the quick set-up procedure. Press [Status]
to return to the operational display.
Start Up and Commissioning
VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark
3-3
3
3