For the D, E, and F Frame sizes, this alarm is based on the
temperature measured by the heatsink sensor mounted
inside the IGBT modules. For the F Frame sizes, this alarm
can also be caused by the thermal sensor in the Rectifier
module.
Troubleshooting
Check fan resistance.
Check soft charge fuses.
IGBT thermal sensor.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The fieldbus on the communication option card is not
working.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and
14-10 Mains Failure
is
NOT set to [0]
No Function
. Check the fuses to the
frequency converter and mains power supply to the unit.
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
the table below is displayed.
Troubleshooting
Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact your Danfoss supplier or
service department. Note the code number for further
troubleshooting directions.
No.
Text
0
Serial port cannot be initialised. Contact your
Danfoss supplier or Danfoss Service Department.
256-258
Power EEPROM data is defective or too old
512
Control board EEPROM data is defective or too old.
513
Communication time out reading EEPROM data
514
Communication time out reading EEPROM data
515
Application oriented control cannot recognize the
EEPROM data.
516
Cannot write to the EEPROM because a write
command is on progress.
517
Write command is under time out
518
Failure in the EEPROM
519
Missing or invalid barcode data in EEPROM
783
Parameter value outside of min/max limits
1024-1279
A centelegram that has to be sent couldn't be
sent.
1281
Digital signal processor flash timeout
1282
Power micro software version mismatch
1283
Power EEPROM data version mismatch
1284
Cannot read digital signal processor software
version
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1301
Option SW in slot C0 is too old
1302
Option SW in slot C1 is too old
1315
Option SW in slot A is not supported (not allowed)
1316
Option SW in slot B is not supported (not allowed)
1317
Option SW in slot C0 is not supported (not
allowed)
1318
Option SW in slot C1 is not supported (not
allowed)
1379
Option A did not respond when calculating
platform version
1380
Option B did not respond when calculating
platform version
1381
Option C0 did not respond when calculating
platform version.
1382
Option C1 did not respond when calculating
platform version.
1536
An exception in the application oriented control is
registered. Debug information written in LCP
1792
DSP watchdog is active. Debugging of power part
data, motor oriented control data not transferred
correctly.
2049
Power data restarted
2064-2072
H081x: option in slot x has restarted
2080-2088
H082x: option in slot x has issued a powerup-wait
2096-2104
H983x: option in slot x has issued a legal
powerup-wait
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
Warnings and Alarms