Voltage mode
Switch S201/switch S202 = OFF (U)
Voltage level
FC 301: 0 to + 10/ FC 302: -10 to +10V (scaleable)
Input resistance, R
i
approx. 10 k
Ω
Max. voltage
±
20V
Current mode
Switch S201/switch S202 = ON (I)
Current level
0/4 to 20 mA (scaleable)
Input resistance, R
i
approx. 200
Ω
Max. current
30 mA
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Max. error 0.5% of full scale
Bandwidth
FC 301: 20 Hz/ FC 302: 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Mains
Functional
isolation
PELV isolation
Motor
DC-Bus
High
voltage
Control
+24V
RS485
18
37
130BA117.10
Pulse/encoder inputs:
Programmable pulse/encoder inputs
2/1
Terminal number pulse/encoder
29
1)
, 33
2)
/ 32
3)
, 33
3)
Max. frequency at terminal 29, 32, 33
110kHz (Push-pull driven)
Max. frequency at terminal 29, 32, 33
5kHz (open collector)
Min. frequency at terminal 29, 32, 33
4Hz
Voltage level
see section on Digital input
Maximum voltage on input
28V DC
Input resistance, R
i
approx. 4k
Ω
Pulse input accuracy (0.1 - 1kHz)
Max. error: 0.1% of full scale
Encoder input accuracy (1 - 11 kHz)
Max. error: 0.05 % of full scale
The pulse and encoder inputs (terminals 29, 32, 33) are galvanically isolated from the supply voltage (PELV) and other high-
voltage terminals.
1)
FC 302 only
2)
Pulse inputs are 29 and 33
3)
Encoder inputs: 32 = A, and 33 = B
Analog output:
Number of programmable analog outputs
1
Terminal number
42
Current range at analog output
0/4 - 20mA
Max. load GND - analog output
500
Ω
Accuracy on analog output
Max. error: 0.5% of full scale
Resolution on analog output
12 bit
The analogue output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS-485 serial communication:
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
FC 300 Selection
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
87
4
4
Содержание VLT AutomationDrive
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT AutomationDrive ...
Страница 280: ...www danfoss com drives MG33BD02 130R0301 MG33BD02 Rev 2011 03 29 ...
Страница 281: ......