8.4.3 Mains Disconnectors, 12-Pulse
Frame size
Power
Type
380-500V
F9
P250
ABB OETL-NF600A
F9
P315
ABB OETL-NF600A
F9
P355
ABB OETL-NF600A
F9
P400
ABB OETL-NF600A
F11
P450
ABB OETL-NF800A
F11
P500
ABB OETL-NF800A
F11
P560
ABB OETL-NF800A
F11
P630
ABB OT800U21
F13
P710
Merlin Gerin NPJF36000S12AAYP
F13
P800
Merlin Gerin NPJF36000S12AAYP
525-690V
F9
P355
ABB OT400U12-121
F9
P400
ABB OT400U12-121
F9
P500
ABB OT400U12-121
F9
P560
ABB OT400U12-121
F11
P630
ABB OETL-NF600A
F11
P710
ABB OETL-NF600A
F11
P800
ABB OT800U21
F13
P900
ABB OT800U21
F13
P1M0
Merlin Gerin NPJF36000S12AAYP
F13
P1M2
Merlin Gerin NPJF36000S12AAYP
8.4.4 F-Frame Mains Contactors
Frame size
Power & Voltage
Type
F3
P450-P500 380-500V & P630-P800 525-690V
Eaton XTCE650N22A
F3
P560 380-500V
Eaton XTCE820N22A
F3
P630380-500V
Eaton XTCEC14P22B
F4
P900 525-690V
Eaton XTCE820N22A
F4
P710-P800 380-500V & P1M2 525-690V
Eaton XTCEC14P22B
WARNING
Customer supplied 230V supply required for Mains
Contactors.
Electrical Installation
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark