Mains Supply 3 x 200 - 240V AC
FC 301/FC 302
P15K
P18K
P22K
P30K
P37K
High/ Normal Load
1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
15
18.5
18.5
22
22
30
30
37
37
45
Enclosure IP20
B4
C3
C3
C4
C4
Enclosure IP21
C1
C1
C1
C1
C1
Enclosure IP55, 66
C1
C1
C1
C2
C2
Output current
Continuous
(3 x 200-240V) [A]
59.4
74.8
74.8
88
88
115
115
143
143
170
Intermittent
(60 sec overload)
(3 x 200-240V) [A]
89.1
82.3
112
96.8
132
127
173
157
215
187
Continuous
kVA (208V AC) [kVA]
21.4
26.9
26.9
31.7
31.7
41.4
41.4
51.5
51.5
61.2
Max. input current
Continuous
(3 x 200-240V) [A]
54
68
68
80
80
104
104
130
130
154
Intermittent
(60 sec overload)
(3 x 200-240V) [A]
81
74.8
102
88
120
114
156
143
195
169
Additional specifications
IP20 max. cable cross-
section
5)
(mains, brake,
motor and load sharing)
35 (2)
50 (1)
50 (1)
150 (300MCM)
150 (300MCM)
IP21, 55, 66 max. cable
cross-section
5)
(mains, motor)
[mm
2
(AWG)]
2)
50 (1)
50 (1)
50 (1)
150 (300MCM)
150 (300MCM)
IP21, 55, 66 max. cable
cross-section
5)
(brake, load
sharing) [mm
2
(AWG)]
2)
50 (1)
50 (1)
50 (1)
95 (3/0)
95 (3/0)
Max cable size with mains
disconnect [mm
2
(AWG)]
2)
50, 35, 35 (1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350MCM, 300MCM,
4/0)
Estimated power loss
at rated max. load [W]
4)
624
737
740
845
874
1140
1143
1353
1400
1636
Weight,
enclosure IP21, 55/66 [kg]
45
45
45
65
65
Efficiency
4)
0.96
0.97
0.97
0.97
0.97
For fuse ratings, see 8.3.1 Fuses
1) High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
2) American Wire Gauge.
3) Measured using 5m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to variety in voltage and
cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the
frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.
(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
5) The three values for the max. cable cross section are for single core, flexible wire and flexible wire with sleeve, respectively.
FC 300 Selection
FC 300 Design Guide
62
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
4