Testing conditions:
EN 60 947-8
Measurement voltage surge resistance
6000V
Overvoltage category
III
Pollution degree
2
Measurement isolation voltage Vbis
690V
Reliable galvanic isolation until Vi
500V
Perm. ambient temperature
-20
°
C ... +60
°
C
EN 60068-2-1 Dry heat
Moisture
5 --- 95%, no condensation permissible
EMC resistance
EN61000-6-2
EMC emissions
EN61000-6-4
Vibration resistance
10 ... 1000Hz 1.14g
Shock resistance
50g
Safety system values:
EN 61508 for Tu = 75
°
C ongoing
SIL
2 for maintenance cycle of 2 years
1 for maintenance cycle of 3 years
HFT
0
PFD (for yearly functional test)
4.10 *10
-3
SFF
78%
λ
s
+
λ
DD
8494 FIT
λ
DU
934 FIT
Ordering number 130B1137
Options and Accessories
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark