Warning
Yellow
Alarm
Flashing red
Trip locked
Yellow and red
Table 6.2 Indicator Light
Bit Hex
Dec
Alarm word
Alarm word 2
Warning word
Warning
word 2
Extended
status word
Alarm Word Extended Status Word
0
00000001
1
Brake check (A28) Servicetrip, read/
write
Brake check (W28) Start delayed Ramping
1
00000002
2
Pwr.card temp
(A69)
Servicetrip,
(reserved)
Pwr.card temp
(A69)
Stop delayed AMA running
2
00000004
4
Earth fault (A14)
Servicetrip,
typecode/spare
part
Earth fault (W14)
Reserved
Start CW/CCW
start_possible is active, when the DI
selections [12] OR [13] are active
and the requested direction
matches the reference sign
3
00000008
8
Ctrl.card temp
(A65)
Servicetrip,
(reserved)
Ctrl.card temp
(W65)
Reserved
Slow down
slow down command active, for
example via CTW bit 11 or DI
4
00000010
16
Ctrl. word TO
(A17)
Servicetrip,
(reserved)
Ctrl. word TO
(W17)
Catch up
catch up command active, for
example via CTW bit 12 or DI
5
00000020
32
Overcurrent (A13) Reserved
Overcurrent (W13) Reserved
Feedback high
feedback >
parameter 4-57 Warning
Feedback High
6
00000040
64
Torque limit (A12) Reserved
Torque limit (W12) Reserved
Feedback low
feedback <
parameter 4-56 Warning
Feedback Low
7
00000080
128
Motor th over
(A11)
Reserved
Motor th over
(W11)
Reserved
Output current high
current >
parameter 4-51 Warning
Current High
8
00000100
256
Motor ETR over
(A10)
Reserved
Motor ETR over
(W10)
Reserved
Output current low
current <
parameter 4-50 Warning
Current Low
9
00000200
512
Inverter overld.
(A9)
Discharge high
Inverter Overld
(W9)
Discharge
high
Output freq high
speed >
10 00000400
1024
DC under volt (A8) Start failed
DC under volt
(W8)
Multi-motor
underload
Output freq low
speed <
parameter 4-52 Warning
Speed Low
11 00000800
2048
DC over volt (A7)
Speed limit
DC over volt (W7) Multi-motor
overload
Brake check OK
brake test NOT OK
12 00001000
4096
Short circuit (A16) External
interlock
DC voltage low
(W6)
Compressor
interlock
Braking max.
BrakePower > Brakepowerlimit
(2-12)
13 00002000
8192
Inrush fault (A33)
Illegal option
combi.
DC voltage high
(W5)
Mechanical
brake sliding
Braking
14 00004000
16384
Mains ph. loss (A4) No safety option Mains ph. loss
(W4)
Safe option
warning
Out of speed range
15 00008000
32768
AMA not OK
Reserved
No motor (W3)
Auto DC
braking
OVC active
16 00010000
65536
Live zero error
(A2)
Reserved
Live zero error
(W2)
AC brake
Troubleshooting
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
181