8-55 Set-up Select
Select the trigger for the set-up selection.
Option:
Function:
[0]
Digital input
A digital input triggers the set-up
selection.
[1]
Bus
A serial communication port or the
fieldbus triggers the set-up
selection.
[2]
Logic AND
The fieldbus/serial communication
port and a digital input trigger the
set-up selection.
[3]
*
Logic OR
The fieldbus/serial communication
port or a digital input triggers the
set-up selection.
8-56 Preset Reference Select
Option:
Function:
Select the trigger for the preset
reference selection.
[0]
Digital input
A digital input triggers the preset
reference selection.
[1]
Bus
A serial communication port or the
fieldbus triggers the preset
reference selection.
[2]
Logic AND
The fieldbus/serial communication
port and a digital input trigger the
preset reference selection.
[3]
*
Logic OR
The fieldbus/serial communication
port or a digital input triggers the
preset reference selection.
8-57 Profidrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
is set to
[0] Digital
and ctrl. word
and
parameter 8-10 Control Word Profile
is set to
[1]
PROFIdrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-58 Profidrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1] PROFIdrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
4.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the frequency converter RS485 port
terminals 68-69.
8-80 Bus Message Count
Range:
Function:
0
*
[0 - 0 ]
This parameter shows the number
of valid telegrams detected on the
bus.
8-81 Bus Error Count
Array [6]
Range:
Function:
0
*
[0 - 0 ]
This parameter shows the number
of telegrams with faults (for
example CRC fault) detected on the
bus.
8-82 Slave Messages Rcvd
Range:
Function:
0
*
[0 - 0 ]
This parameter shows the number
of valid telegrams addressed to the
slave sent by the frequency
converter.
8-83 Slave Error Count
Range:
Function:
0
*
[0 - 0 ]
This parameter shows the number
of error telegrams, which are not
executed by the frequency
converter.
8-84 Slave Messages Sent
Range:
Function:
0
*
[0 - 0 ]
This parameter shows the number
of messages sent from the slave.
Parameter Descriptions
Programming Guide
MG06J202