14-90 Fault Level
This is an array parameter with 26 elements. Each of the bits can
be configured to any of the following options. Use this
parameter to customize fault levels.
Option:
Function:
[2]
Trip
Changing a fault level from default
option
[3] Trip Lock
to
[2] Trip
leads
to the automatic reset of the alarm.
For alarms involving overcurrent,
the frequency converter has a
hardware protection that issues a 3-
minute recovery after 2 consecutive
overcurrent incidents. This hardware
protection cannot be overruled.
[3]
Trip Lock
14-90 Fault Level
This is an array parameter with 26 elements. Each of the bits can
be configured to any of the following options. Use this
parameter to customize fault levels.
Option:
Function:
[4]
Trip w.
delayed reset
This option adds a delay between
automatic resets, otherwise it is the
same as option
[2] Trip
. The delay
prevents a situation where reset is
attempted repeatedly for an
overcurrent situation. Hardware
protection of the frequency
converter forces the 3-minute
recovery time after 2 consecutive
overcurrents (within a short time
window).
Failure
Alarm
Element in
Off
Warning
Trip
Trip Lock
Trip with
delayed
reset
10 V low
1
1490.0
X
D
–
–
–
24 V low
47
1490.1
X
–
–
D
–
1.8 V supply low
48
1490.2
X
–
–
D
–
Voltage limit
64
1490.3
X
D
–
–
–
Ground fault during ramping
14
1490.4
–
–
D
X
–
Ground fault 2 during cont.
operation
45
1490.5
–
–
D
X
–
Torque limit
12
1490.6
X
D
–
–
–
Overcurrent
13
1490.7
–
–
X
D
–
Short circuit
16
1490.8
–
–
X
D
–
Heat sink temperature
29
1490.9
–
–
X
D
–
Heat sink sensor
39
1490.10
–
–
X
D
–
Control card temperature
65
1490.11
–
–
X
D
–
Power card temperature
69
1490.12
–
–
X
D
–
Heat sink temperature
244
1490.13
–
–
X
D
–
Heat sink sensor
245
1490.14
–
–
X
D
–
Power card temperature
247
1490.15
–
–
X
D
–
Motor phase missing
30–32
1490.16
–
–
X
D
–
Locked rotor
99
1490.20
–
–
D
X
–
Table 4.18 Selection of Action when Selected Alarm Appears
MCT 10 Set-up Software has the element numbers listed in the column ID. Use this table together with MCT 10 Set-up Software to get information
about specific fault levels.
D stands for the default setting.
X stands for a possible option.
Parameter Descriptions
VLT® AutomationDrive FC 361
138
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4