6-50 Terminal 42 Output
Option:
Function:
[137] Speed
4-20mA
Taken from
. 20 mA = value in
parameter 3-03 Maximum Reference
[139] Bus ctrl.
0-20 mA
An output value set from fieldbus process
data. The output works independently of
internal functions in the frequency
converter.
[140] Bus ctrl.
4-20 mA
An output value set from fieldbus process
data. The output works independently of
internal functions in the frequency
converter.
[143] Ext. CL 1
4-20mA
[150] Max Out Fr
4-20mA
0 Hz = 0 mA,
= 20 mA.
[254] DC Link
0-20mA
[255] DC Link
4-20mA
Enable the function of outputting the DC-
link voltage on analog outputs. It scales the
output according to the maximum and
minimum voltage of the current drive size.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0 %
*
[0 - 200 %]
Scale for the minimum output (0
mA or 4 mA) of the analog signal
at terminal 42.
Set the value to be the percentage
of the full range of the variable
selected in
parameter 6-50 Terminal
42 Output
.
6-52 Terminal 42 Output Max Scale
Range:
Function:
100 %
*
[0 - 200 %]
Scale the maximum output of the
selected analog signal at terminal
42. Set the value to the maximum
value of the current signal output.
Scale the output to give a current
lower than 20 mA at full scale; or
20 mA at an output below 100% of
the maximum signal value. If 20 mA
is the required output current at a
value 0–100% of the full-scale
output, program the percentage
value in the parameter, that is 50%
= 20 mA. If a current 4–20 mA is
required at maximum output
(100%), calculate the percentage
value as follows:
20 mA/desired maximum current x 100 %
i . e . 10 mA : 20
10 x 100 = 200 %
e30ba075.14
(mA)
0%
20
0/4
100%
Current
Analog
output
min scale
par. 6-51
Variable for
output
example:
Speed (RPM)
Analog
output
max scale
par. 6-52
Illustration 4.33 Output Max. Scale
6-53 Terminal 42 Output Bus Control
Range:
Function:
0 %
*
[0 - 100 %]
Holds the level of output 42 if
controlled by bus.
6-54 Terminal 42 Output Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %]
Holds the preset level of output 42.
If a timeout function is selected in
parameter 6-50 Terminal 42 Output
,
the output is preset to this level if a
fieldbus timeout occurs.
6-55 Analog Output Filter
Option:
Function:
The following readout parameters
from selection in
parameter 6-50 Terminal 42 Output
have a filter selected when
parameter 6-55 Analog Output Filter
is on:
Selection
0–20
mA
4–20
mA
Motor current
(0–I
max
)
[103]
[133]
Torque limit (0–
T
lim
)
[104]
[134]
Rated torque (0–
T
nom
)
[105]
[135]
Power (0–P
nom
)
[106]
[136]
Speed (0–
Speed
max
)
[107]
[137]
Table 4.15 Readout Parameters
[0]
*
Off
Filter off.
[1]
On
Filter on.
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
85
4
4
Содержание VLT AutomationDrive FC 361
Страница 2: ......