4.12.4 13-4* Logic Rules
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in
parameter 13-40 Logic
Rule Boolean 1
,
parameter 13-42 Logic Rule Boolean 2
, and
parameter 13-44 Logic Rule Boolean 3
. Define the operators
used to logically combine the selected inputs in
parameter 13-41 Logic Rule Operator 1
and
parameter 13-43 Logic Rule Operator 2
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 4.39 Logic Rules
Priority of calculation
The results of
parameter 13-40 Logic Rule Boolean 1
,
parameter 13-41 Logic Rule Operator 1
, and
parameter 13-42 Logic Rule Boolean 2
are calculated first.
The outcome (true/false) of this calculation is combined
with the settings of
parameter 13-43 Logic Rule Operator 2
and
parameter 13-44 Logic Rule Boolean 3
, yielding the final
result (true/false) of the logic rule.
13-40 Logic Rule Boolean 1
Option:
Function:
[0]
False
Select the first boolean (true or
false) input for the selected logic
rule.
See
parameter 13-01 Start Event
and
parameter 13-02 Stop Event
for more
information.
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed
low
[12]
Above speed
high
13-40 Logic Rule Boolean 1
Option:
Function:
[13]
Out of feedb.
range
[14]
Below feedb.
low
[15]
Above feedb.
high
[16]
Thermal
warning
[17]
Mains out of
range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip
lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input
DI18
[34]
Digital input
DI19
[35]
Digital input
DI27
[36]
Digital input
DI29
[37]
Digital input
DI32
[38]
Digital input
DI33
[39]
Start
command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
Ok key
[OK] is pressed. Only available on
the graphical LCP.
[44]
Reset key
[Reset] is pressed. Only available on
the graphical LCP.
[45]
Left key
[
◄
] is pressed. Only available on the
graphical LCP.
[46]
Right key
[
►
] is pressed. Only available on the
graphical LCP.
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
121