1.3.2 Pulse Start/Stop
Terminal 18 =
Parameter 5-10 Terminal 18 Digital Input
,
[9]
Latched start
.
Terminal 27 =
Parameter 5-12 Terminal 27 Digital Input
,
[6]
Stop inverse
.
12 13 18
e30bg748.10
32
27
19
29
33
20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
S tar t
S t op in v erse
S tar t (18)
S tar t (27)
Illustration 1.7 Pulse Start/Stop
1.3.3 Speed up/Speed Down
Terminals 29/32 = Speed up/Speed down
Terminal 18 =
Parameter 5-10 Terminal 18 Digital
Input
[9] Start
(default).
Terminal 27 =
Parameter 5-12 Terminal 27 Digital
Input
[19] Freeze reference
.
Terminal 29 =
Parameter 5-13 Terminal 29 Digital
Input
[21] Speed up
.
Terminal 32 =
Parameter 5-14 Terminal 32 Digital
Input
[22] Speed down
.
NOTICE
Terminal 29 only in FC x02 (x=series type).
12
18
27
29
32
+24V
P ar . 5-10
P ar . 5-12
P ar . 5-13
P ar . 5-14
e30bg749.10
Illustration 1.8 Speed up/Speed down
1.3.4 Potentiometer Reference
Voltage reference via a potentiometer
Reference source 1 =
[1] Analog input 53
(default).
Terminal 53, low voltage = 0 V.
Terminal 53, high voltage = 10 V.
Terminal 53, low reference/feedback = 0 RPM.
Terminal 53, high reference/feedback = 1500 RPM.
Switch S201 = OFF (U)
130BA154.11
55
50
39 42
53 54
Speed RPM
P 6-15
1 k
Ω
+10V/30mA
Ref. voltage
P 6-11 10V
Illustration 1.9 Potentiometer Reference
Introduction
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
9